Data sheet / Instruction
E N G L I S H
1. Overshoot clamp kit
The output choke limits the motor voltage dU/dt on the motor terminals to <500V/
clamp limits, in combination with the necessary output choke, the voltage at U2, V2 and W2 to 100V
max. above the DC-Link voltage.
NOTE: The option DC+/DC- is required to be able to connect the Overshoot clamp in frame
sizes B to F and C2 to F2.
Part No : 052163
Fig. 1 Overshoot clamp kits
Part number 052163 - Overshoot clamp kit for Emotron FDU/VFX AC drives, frame size
B to F and C2 to F2.
The overshoot clamp kit includes:
1 pc - Overshoot clamp unit
2 pcs - DC Fuse holder (with fuses) including DIN rail
2 pcs - cables for connection between DC Fuses and PEBB
Part number 052220 - Overshoot clamp kit for Emotron FDU/VFX AC drives, frame size
G and up.
The overshoot clamp kit includes:
1 pc - Overshoot clamp unit
2 pcs - DC Fuse holder (with fuses) including DIN rail
1 pc - mounting plate for DC-fuse holder
2 pcs - cables for connection between DC Fuse holder and PEBB DC+/DC-
2 pcs - Screws M6 x 10 for connecting the cables to the DC terminals on the PEBB.
CG Drives & Automation, 01-5933-11r0
Part No : 052220
μ
s. The overshoot