13.
Seal the gap around the cover support collar [12] with a continuous bead of electrical grade type RTV silicone sealant.
14.
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical grade type RTV silicone
sealant around the perimeter on the underside of the cover flange [14].
15.
Attach flange [14] to the cover support collar [12] using #8-32 flat head screws [15] provided with the cover, see
FIGURE J. Tighten mounting screws [15] to 10 - 15 lbs-in torque [1.1 - 1.7 N m].
16.
For multi-service applications, mount the extension assembly [16] to the furniture feed cover [17] as shown in FIGURE
K using the supplied #6-32 x 1/4" pan head screws [18]. Tighten mounting screws to 9 - 12 lbs-in torque [1.0 - 1.3
N m]. Extension assembly is not required for single service applications.
17.
Configure furniture feed cover [17] using supplied conduit fittings [19] and/or plugs. Openings must always be
plugged when not in use. Apply pipe thread tape or sealant on fittings prior to installation in the threaded hole.
Tighten fully to ensure seal.
18.
Feed wires up through the cover [17] and fittings [19].
19.
Fasten cover to feed cover flange with three oval screws [20] provided. Tighten mounting screws to 9 - 12 lbs-in
torque [1.0 - 1.3 N m].
19
17
15
12
FIGURE
J
20
14
SEAL ALL AROUND
18
FIGURE
K
CFBS1R6FFCVR FURNITURE FEED COVER FOR 2 GANG RECESSED
CONCRETE FLOOR BOX Installation Instructions
CAUTION: NOT FOR USE WITH FIRE RATED POKE-THROUGHS. Use S1R6FFCVRxx covers for fire rated poke-through
furniture feed applications.
CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with all national and local electrical codes,
communications standards, the following instructions and any instructions included with individual devices.
NOTICE: Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC
and CE Code requirements.
Use with CFB2G25R, CFB2G25RCR, CFB2G30R, or CFB2G30RCR floor boxes.
Also compatible with CFB2G25, CFB2G25CR, CFB2G30, and CFB2G30CR floor boxes when used with the
CFB2GS1R6ADAPT adapter.
AFTER CONCRETE POUR
1.
Locate floor box, remove three screws [1] and temporary concrete cover [2], see FIGURE A. CAUTION: Temporary
concrete covers are intended to keep concrete residue from entering box during pour and are not intended to
support loads. Replace with permanent flange/cover immediately after concrete has hardened.
2.
Pull and dress wires. If grounded metallic conduit is used, connect green grounding lead [3] to device ground, see
FIGURE B. For a non-metallic conduit system, pigtail a separate grounding wire to the grounding lead [3] to ground
the box and cover.
3.
For single service applications, go to step 10.
1
17
FIGURE
A
16
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2546
04/14
2
3
FIGURE
B
ENGLISH

Publicidad

loading

Resumen de contenidos para Hubbell CFBS1R6FFCVR

  • Página 1 CFBS1R6FFCVR FURNITURE FEED COVER FOR 2 GANG RECESSED Seal the gap around the cover support collar [12] with a continuous bead of electrical grade type RTV silicone sealant. Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical grade type RTV silicone CONCRETE FLOOR BOX Installation Instructions sealant around the perimeter on the underside of the cover flange [14].
  • Página 2 Remove appropriate tab [4] from furniture feed plate [5] to clear floor box wiring channel [6], see FIGURES C & D. For multi-service applications, orient cover support collar [12] to the position shown in FIGURE G by removing and Wiring channel must be installed in multi-service applications. reinstalling four screws [13].
  • Página 3 COUVERCLE DE BO TE DE PLANCHER ENCASTR E DANS LE B TON DEUX Sceller le vide autour du collier de soutien du couvercle [12] en appliquant un cordon continu de p te calfeutrer la COMPARTIMENTS POUR L ALIMENTATION DU MOBILIER CFBS1R6FFCVR silicone de type RTV pour applications lectriques.
  • Página 4 Retirer la patte [4] appropri e de la plaque d'alimentation du mobilier [5] pour d gager la canalisation de c blage [6] Dans le cas d'utilisations multiservices, orienter le collier de soutien du couvercle [12] vers la position indiqu e la dans la bo te de plancher, consulter les FIGURES C et D.
  • Página 5 FIGURA Wiring Device - Kellems HUBBELL DE M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el Hubbell Incorporated (Delaware) art culo a su juicio en un plazo de 60 d as.
  • Página 6 Retirar la pesta a apropiada [4] de la placa de alimentaci n para mueble [5] para despejar el canal de cableado de la Para aplicaciones de m ltiples servicios, orientar el collar n de soporte de la tapa [12] en la posici n mostrada en caja para pisos [6], ver FIGURAS C y D.

Este manual también es adecuado para:

Cfbs1r6ffcvralu