Ceiling Fan-Light
MODEL: 763RLN & 769RL
SUITABLE FOR USE OVER TUB OR SHOWER ENCLOSURE
WHEN INSTALLED IN A GFCI PROTECTED BRANCH CIRCUIT.
I M P O R TANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
F O L L O W I N G :
A. Use this unit only in the manner intended by the manufacturer. If you
have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at service panel and
lock service panel to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the service panel.
C A U T I O N :
For general ventilating use only. Do not use to exhaust hazardous or
explosive materials and vapors
I N S TA L L ATION INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
F O L L O W I N G :
A. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
B. Sufficient air is needed for proper combustion and exhausting of gases
through the flue (chimney) of fuel burning equipment to prevent back
drafting. Follow the heating equipment manufacturer's guideline and
safety standards such as those published by the National Fire
Protection Association (NFPA), and the American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE), and the local
code authorities.
C. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
D. Ducted fans must always be vented to the outdoors.
E. If this unit is to be installed over a tub or shower, it must be marked as
appropriate for the application.
F. NEVER place a switch where it can be reached from a tub or shower.
• Unit consists of the housing, power unit/blower assembly (motor, wheel
mounting plate, grille, reflector, lens and duct collar).
• WARNING: To reduce the risk of fire or electric shock, do not use
this fan with any solid-state speed control device.
• WARNING: To reduce the risk of shock, disconnect power before
s e r v i c i n g .
• Not for use in kitchens.
• Do not install in a ceiling insulated to a value greater than R-40.
• For installation in sloped ceilings up to 7/12 pitch, ductwork must point up.
FOR BEST RESULT S
For new construction install the housing during the rough-in stage of
construction. The blower unit, light and grille should be installed after the
finished ceiling is in place.
To install the Exhaust Fan-Light in an existing finished building requires
an accessible area (attic or crawl space) above the planned location.
.
INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
PLANNING DUCTWORK AND WIRING
D U C T W O R K
1. Use 4" round duct.
2. Plan to run duct from the fan's discharge opening to the outside. For
best fan performance, make duct run as short as possible and use
minimum number of elbows.
3. Use optional NuTone ducting accessories as needed (refer to NuTo n e ' s
catalog for a complete listing of optional accessories).
W I R I N G
Plan to run 120vAC house wiring (with ground) from a power source,
through a standard wall switch or an optional NuTone double FAN/LIGHT
switch, to the junction box in the Fan-Light's housing.
I N S TA L L ATION IN A NEW
CONSTRUCTION SITE
P R E PA R AT I O N
1. Unplug the power unit.
2. Refer to Figure 1. Remove power unit/blower assembly from the
housing. Remove screw and pull power unit assembly tabs out of slots
in housing. Set unit aside until needed.
3. Remove one of the wiring knockouts from housing.
MOUNTING THE HOUSING
USING SIDE MOUNTING TA B S
Refer to Figure 2.
1. Locate housing next to ceiling joist.
2. Use wood screws (not provided) to loosely attach housing to ceiling
joist through keyhole slots in mounting tabs.
3. Adjust housing so that it will be flush with the finished ceiling.
4. When housing is properly adjusted, tighten screws in slots.
USING HANGER BARS
(Hanger bars sold separately, order model HB4)
Refer to Figure 3.
1. Insert hanger bars in slots provided in housing.
2. Locate fan housing between ceiling joists so that bottom of fan housing
is even with the planned finished ceiling.
3. Use screws or nails to secure mounting brackets to ceiling joists.
I N S TALLING DUCTWORK
1. Refer to Figure 1. Place duct collar over flanges at discharge opening
of fan. Secure collar by snapping tabs into slots in flanges.
2. Refer to Figure 4. Run 4" round duct from outside to fan's discharge
o p e n i n g .
3. Connect duct to duct collar.

Publicidad

Tabla de contenido
loading

Resumen de contenidos para NuTone 763RLN

  • Página 1 F O L L O W I N G : A. Use this unit only in the manner intended by the manufacturer. If you 3. Use optional NuTone ducting accessories as needed (refer to NuTo n e ' s have questions, contact the manufacturer.
  • Página 2: Completing Insta L L At I O N

    2. To control both fan and light with one switch, install wiring. planned installation location. 3. For separate control of the fan and light, use NuTone double switch and Plan ducting and wiring before proceeding with installation (see install wiring.
  • Página 3: Instrucciones Importantes De Seguridad

    VENTILADOR/LAMPARA materiales y vapores peligrosos o explosivos. opcional de NuTone, a la caja de empalme de la caja de la Lámpara- V e n t i l a d o r . INSTRUCCIONES DE INSTA L A C I O N...
  • Página 4: I N S Ta L Atcion Del Conducto

    3. Para el control separado del ventilador y de la luz, utilice un interruptor planeado para asegurarse de que: doble de NuTone e instale el cableado. 4. Instale un conectodor de caja aprobado en el agujero de acceso al ( 1) El conducto se puede instalar cableado.
  • Página 5: Pour De Meilleurs Résultats

    A . Utilisez cet unité seulement comme indiquée par le fabricant. Si vous 3. Utilisez les accessoires de gaine en option NuTone, si nécessaire. avez de questions, contactez le fabricant. (Consultez le catalogue NuTone pour une liste complète B .
  • Página 6: Installation Dans Une Construction Existante

    3. Pour une commande séparée du ventilateur et de l’éclairage, utilisez (2) Le câblage peut être acheminé vers l’endroit choisi. l’interrupteur double de NuTone et installez le câblage. (3) Aucun câblage ou autre obstruction peut empêcher l’installation 4. Montez un presse-étoupe homologué dans la découpe de câblage.
  • Página 7 DUCT COLLAR HOUSING HANGER BARS (SOLD Collarin Del Conducto Caja SEPARATELY) COL DE GAINE HABITACLE La Barras De Suspensión Se Vende Por Separado LES BARRES DE HANGER BARS SUSPENSION SONT (SOLD SEPARATELY) VENDUES SÉPARÉMENT La Barras De Suspensión Se Vende Por Separado LES BARRES DE SUSPENSION SONT VENDUES...
  • Página 8: Parts List

    LIGHT RECEPTACLE 763RLN, 769RL 8 2 3 0 4 - 0 0 0 NuTone Attn: Parts Department 4820 Red Bank Rd. NOTE: Always order by Cincinnati, OH 45227-1599 current part number Phone: (513) 527-5426 Fax: (513) 527-5173 763RLN & 769RL I.I.

Este manual también es adecuado para:

769rl

Tabla de contenido