KZ700 Mounting Base Installation Sheet
EN DE ES FR
IT
NL PL PT RU SV
1
EN: Installation Sheet
Description
This document includes installation information for the KZ700
Mounting Base for conventional detectors. For pipe installation
the S700 pipe installation mount (not supplied) is required.
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use, and maintenance, refer to the
EN 54-14 standard and local regulations.
Connection
Connect the line as follows:
•
Terminal 1 – Line in / out (positive)
•
Terminal 3 – Line out (negative)
•
Terminal 4 – Line in (negative)
Connect remote indicators as follows:
•
Terminal 1 – Remote indicator (positive)
•
Terminal 2 – Remote indicator (negative)
See Figure 1.
Cabling requirements
WARNING:
To ensure correct operation of your system, you
must follow the recommended cabling practices described
below.
© 2015 UTC Fire & Security. All rights reserved.
The cable used should:
•
Have a cross-sectional area of at least 1.5 mm²
Have maximum resistance of 13.3 Ω / km per core
•
Maintenance
Basic maintenance consists of a yearly inspection.
Specifications
Number of terminals
Earth contact
Remote indicator connection
IP rating
Operating temperature
Storage temperature
Relative humidity
Dimensions (Ø × H)
Regulatory information
Certification
Manufacturer
United Technologies Safety System Co. Ltd
80, Changjiang East Road, QETDZ,
Qinhuangdao, Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
1 / 8
4
No
Yes
IP30
−10 to +50ºC
−10 to +70ºC
10 to 95% noncondensing
103 x 23 mm
P/N 10-4221-501-KZ70-01 • ISS 25FEB15