Installation
WARNING
Warning of cutting injuries!
Danger of cutting injuries when handling blades. Wear protective gloves!
Fig. 2.1
Cut ClimaForm in the top right section by 30 mm around the outline of the motor flange.
Use a suitable blade.
Fig. 2.2
Clean the motor flange of the pump and Armaflex strips using special cleaner for Armaflex.
Initially apply a thin, even layer of Armaflex 520 adhesive to the Armaflex strip of the pump's
motor flange.
Check the flash off time with your fingers!
Fig. 2.3
Carefully apply Armaflex strips without any tension to the centre of the motor flange and apply
moderate pressure.
Strips must overlap by approximately 10 mm. Whilst doing so, ensure condensate drainage
outlets on the pump housing are not covered!
Fig. 2.4a Position Wilo-ClimaForm around the pump housing.
Apply a thin, even layer of Armaflex 520 adhesive to the slot surfaces of the sensor cable duct.
Subsequently insert the cable into the slot and press the adhesive surfaces together by apply-
ing moderate pressure (wet bonding).
Avoid movement of the sensor cable as a result of tension!
Fig. 2.4b Apply a thin, even layer of Armaflex 520 adhesive to both ClimaForm cutting surfaces.
Fig. 2.5
Check the flash off time of the adhesive with your fingers. The adhesive must no longer form
strings between adhesive surface and fingers.
Fig. 2.6
Fold the ClimaForm once adhesive flash off is complete and press together by applying moder-
ate pressure.
Fig. 2.7
Apply a thin and even layer of Armaflex 520 adhesive to the motor flange and ClimaForm con-
nection surface.
Press the connection surface onto the motor flange (wet bonding).
Fig. 2.8
Stick the Armaflex tape (width 100 mm) supplied over the seam contour of the two halves of
the mould below the condensate drainage outlet of the motor housing.
ƒ
Place the tape with the upper cut edge against the contour of the transition from the mo-
tor housing to the ClimaForm and apply moderate pressure to press it down from top to
bottom over its entire surface along the adhesive seam. Press the tape into the recessed
part of the ClimaForm using a flat scraper.
ƒ
Either cut off (1) the excess tape or fold it over (2).