Owner's Manual Addendum
Portable Air Conditioning Unit
Low Temperature Operation
The SRCOOL12K is a high performance cooler, capable of producing very cold air output. When using the SRCOOL12K in environments that are
already cold (20° C / 68° F or less), Tripp Lite recommends using the Dehumidify Mode only. This will allow the unit to continue to provide the
supplemental cooling while preventing any evaporator icing issues caused by the low room temperature.
Additional Display Error Codes
The Tripp Lite SRCOOL12K has the ability to continually monitor itself. Should an error occur, the display will show one of 5 error codes below:
Error Code
Description
E0
Internal Communication Error
E1
Indoor Temperature Sensor Error
E2
Internal Temperature Sensor Error
E3
Refrigerant Error
E4
Water Full
Code E4 can be cleared by emptying the water tank. Consult the owner's manual for details.
For Codes E0, E1, E2, and E3 follow these steps:
1. Power cycle the unit by unplugging it from the source for 5 minutes.
2. Plug the unit back in.
3. Restart the unit.
If the code remains clear, continue to operate the unit as normal. If the code returns, please contact Tripp Lite for further instructions.