Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
34
Z. 1
Z. 2 Z. 3
Z. 4
Z. 5 Z. 6
Z. 7
22
32
42
52
62
72
Zone x - ON/OFF
On/Off
This communication object allows modifying the zone operation status, turning the
zone indicated Off or On.
0 → Zone OFF; 1 → Zone ON
Reading/Writing
1.001
Z. 1
Z. 2 Z. 3
Z. 4
Z. 5 Z. 6
Z. 7
23
33
43
53
63
73
Zone x - Set Temperature
Temperature
This communication object allows defining the set point temperature value. This value
can be modified in the corresponding zone of the system.
Degrees Celsius format: 18ºC... 30ºC, with a resolution of 0.5ºC
Fahrenheit format: 64F... 86F, with a resolution of 1F
Reading/Writing
9.001
Z. 1
Z. 2 Z. 3
Z. 4
Z. 5 Z. 6
Z. 7
24
34
44
54
64
74
Zone x - Local temperature
Temperature
This communication object allows defining the local temperature value in the
corresponding zone of the system.
For a certain zone to be working without having an Airzone's element that measures
the temperature (tacto/probe), it is necessary to introduce the room temperature value
through this communication object.
0ºC... 99.9ºC, with a resolution of 0.1ºC
Reading/Writing
9.001
Z. 8
Z. 9 Z. 10 Z. 11 Z. 12 Z. 13 Z. 14 Z. 15 Z. 16 Z. 17 Z. 18 Z. 19 Z. 20 Z. 21 Z. 22 Z. 23
82
92
102
112
122
132
142
Z. 8
Z. 9 Z. 10 Z. 11 Z. 12 Z. 13 Z. 14 Z. 15 Z. 16 Z. 17 Z. 18 Z. 19 Z. 20 Z. 21 Z. 22 Z. 23
83
93
103
113
123
133
143
Z. 8
Z. 9 Z. 10 Z. 11 Z. 12 Z. 13 Z. 14 Z. 15 Z. 16 Z. 17 Z. 18 Z. 19 Z. 20 Z. 21 Z. 22 Z. 23
84
94
104
114
124
134
144
152
162
172
182
192
202
212
153
163
173
183
193
203
213
154
164
174
184
194
204
214
222
232
242
223
233
243
224
234
244