The kit is composed of:
- A rail DIN
- A circuit breaker
- A transformer
- A gateway MODBUS /LON
The entire kit is supplied pre-wired.
As the layout of cabinets for machines is optimised, we recommend installing the kit in a cabinet outside the unit.
The cabinet must be placed in a room where the temperature is kept at between 0°C and 50°C.
Description of the LON data available with the name of variables
Outdoor temperature
On/Off
Setpoint 1 /Setpoint 2 control
Type of coil 1
Type of coil 2
Fan fault, stage 1, line 1
Fan fault, stage 2, line 1
Fan fault, stage 3, line 1
Fan fault, stage 4, line 1
Fan fault, stage 5, line 1
Fan fault, stage 6, line 1
Fan fault, stage 1, line 2
Fan fault, stage 2, line 2
Fan fault, stage 3, line 2
Fan fault, stage 4, line 2
Fan fault, stage 5, line 2
Fan fault, stage 6, line 2
Fan status, stage 1, line 1
Fan status, stage 2, line 1
Fan status, stage 3, line 1
Fan status, stage 4, line 1
Fan status, stage 5, line 1
Fan status, stage 6, line 1
POWER SUPPLY
LON WORKS TO BMS
230 V - 50 HZ
230V
Transformer
Circuit-breaker
230 V - 400 V
2P 1A
24V - 40VA
24V
Parameters list for controller
Dry-Cooler / Condenser
1
2
3
4
5
G
GO
C1
C2
Tx+
0V
0V
LON Gateway
EN - 2
MODBUS WORKS
1000 maxi
6
Tx-
nvo
(Reading)
nvoTempExt
nvoOnOff
nvoRegulCons1ou2
nvoTypeBat1
nvoTypeBat2
nvoDefVentE1L1
nvoDefVentE1L2
nvoDefVentE2L1
nvoDefVentE2L2
nvoDefVentE3L1
nvoDefVentE3L2
nvoDefVentE4L1
nvoDefVentE4L2
nvoDefVentE5L1
nvoDefVentE5L2
nvoDefVentE6L1
novDefVentE6L2
nvoMarcheVentE1L1
nvoMarcheVentE1L1
nvoMarcheVenE2L1
nvoMarcheVenE2L1
nvoMarcheVenE2L1
nvoMarcheVenE3L1