58102
Product presentation
1 Base
2 Cover
3 Cover fastening screws
4 Knob
5 Locking pins
6 Index
The locking pins 5 permit limitation of the scale
and are lodged in the fastening holes on the
plastic base of the thermostat.
Installation
The room thermostat must be installed at
approximately 1,5 metres up from floor upon an
interior wall, away from direct solar radiation and
any heat source such as television, lighting and air
draught etc.
Operation
The desired temperature can be set by positioning
the knob on the graduated scale.
The 58102 is provided with three switches:
• The ON/OFF switch that, in addition to
switching the thermostat on and off, restores
and interrupts power on the outside loads.
• Three-position switch: heating
ventilation
, cooling
.
• Three-position switch for the three fan speeds:
,
and
.
The thermostat is equipped with an ON/OFF
indicator light and a light that signals activation of
the load, located near the setting dial.
The thermostats are normally provided with
the JP1 jumper off, that is, with ON-OFF type
adjustment. With JP1 on control is have a
proportional type.
Connections
Continuous operation of the fan at the selected
speed controlled:
• in the winter, by the remote resistor command (3)
• in the summer,by the water delivery (2)
• delivery solenoid valve with jumper JP1 on.
• on the motor driven valve with JP1 off
The jumper CV3-CV4 should be in the position
indicated in the drawing with "CV3 ON".
2
Thermostat d'ambiance pour la
a
climatisation
Room thermostat for air conditioning
z
Thermostat für die
e
Raumklimatisierung
Termostato ambiente per la
y
climatizzazione
Termóstato de ambiante para la
r
climatizacióne
Operation of the fan (1) at the preset speed depen-
ding on the temperature. Jumper JP1 has to be
off (jumper CV3-CV4 should be in the position
indicated in the drawing with "CV4 ON").
,
Continuos operation of the fan (1) at the selected
speed controlled by the water delivery (2):
• delivery solenoid valve with jumper JP1 on.
• on the motor driven valve with JP1 off
The jumper CV3-CV4 should be in the position
indicated in the drawing with "CV3 ON".
Temperature's scale adjustement
• After two days from the installation, measure
the room temperature with a reference
thermometer.
• Draw back the knob and locate it to reach
vthe same value of the reference thermometer.
Technical specifications
Power supply :
220-240V v 50/60Hz
Temperature setting range :
Differential:
Speed of variation of temperatures:
Outputs for adjustment by relay with NA contact:
Output for fan operation:
controlled by a switch at 1T 5(2)A 250V v
The total load of the device should not, in any case,
exceed 5(2)A 250V v
Connection by terminals on a printed circuit with
higher capacity than 5(2)A 250V v
Working temperature:
from 0 °C to +50 °C
with relative humidity (0-90%)
Storage temperature:
from –20 °C to +70 °C
IP30
Group of insulation material:
Fastening to the wall by screws
Automatic control device by independent mounting
Cassification according to the characteristics of
automatic operation:
Duration of electric stress for insulation parts:
Device for use under conditions of normal pollution
Isolation class:
Upstream protection :
Software structure :
Pollution category :
Rated impulse voltage :
Ecodesign class :
Voltage and current declared for the needs of EMC
emissions tests :
Independent installation device for built-in installation
Made in France
from 5 to 30 °C
0,25°K
>1°K/15 min.
1T 5(2)A 250V v
III a
1B
long period
II
circuit breaker 6A
class A
2
4kV
IV
230V v - 0,5A
6LE004171A