Fig. 1. Valve closed.
Fig. 2. Opened 2.3 turns.
Fig. 3. Fully open valve.
Fig. 4. Recommended installation
Presetting
The presetting of a valve for a certain pressure drop (e.g.
corresponding to the presetting position 2.3) should be carried out as
follows:
1. Close the valve fully (Fig. 1).
2. Open the valve 2.3 turns (Fig. 2).
3. Using a 3 mm Allen key, turn the inner spindle clockwise to its end
position.
4. The valve is now preset.
A pressure drop diagram is available for each valve size, showing the
pressure drop curves for various settings and flows.
= Recommended direction of flow for best accuracy.
Draining
There is a recess for a 5 mm Allen key under the cover.
Turn 8-14 turns to drain.
Valves without draining can be equipped with a draining kit, article No.
52 179-990 (G1/2) or 52 179-996 (G3/4), provided that the valve
is prepared for draining. The draining kit can be installed during
operation.