2 DESCRIPTION
2.1 Overview
1
a
i
s
s
o
n
3
2.2 Technical data
2.2.1
Operation
▪
Single phase 230 VAC, 50 Hz
▪
Maximum output for URBAN model housings: 1450 W
▪
Electrical protection index for Cube housings: IPX2
▪
Electrical protection index for URBAN housings: IP20
▪
Ambient operating temperature: -5°C/60°C
▪
Communication Radio:
o Wireless Protocol N°1: 868.3MHz
o Wireless Protocol N°2: 2400MHz à 2483.5MHz / -2dBm
2.2.2 Structure
▪
Weight: 8.2 kg (Urban)
▪
Housing Urban:
o Housing and wall mount: electrolytic zinc coated sheet, th. 0.6 mm or 1 mm or 2 mm
– epoxy powder-coated paint RAL 9003
o Structure: Aluzinc sheet, 1.2 mm or 1 mm
o Side with the Drawer, Power access hatch, Trim and Front panel: ABS/PC UL94V0
o Internal structure: PPE 60 g/l
▪
Grade F7 filters
2.2.3 Performance
▪
Air preheating:
o VMI® unit: X, 12°C, 15°C, 18°C (manual programming)
▪
Maximum flow rate for Urban model: 202 m3/h
▪
Recommended size of premises to be ventilated: from 50 m² to 120 m²
(Average renewal rate 0.5 vol/h, unchanging ceiling height of 2.5 m)
4
5
▪
Control unit : 7.08 dBm ERP
▪
VMI : 0.37 dBm ERP
1 – Housing
2 – Air inlet (Wall-mount side) -
suction
3 – Air outlet
4 – Power access hatch (access to
the junction box)
5 – Filter drawer
*Non-contractual drawing
2
*Urban housing
a
i
s
s
o
n
20