Piping Length & Elevation
If the pipe is too long, both capacity and reliability of the unit will drop. As the number of bends increases, resistance to the
fl ow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always
choose the shortest path and not exceed the maximum piping length as tabulated below.
Model
Maximum
Total Piping
Length (m)
5MSY20B/BR
L
(2 Ports)
1
5MSY25B/BR
L
1
(3 Ports)
5MSY30B/BR
L
+ L
1
(4 Ports)
INDOOR UNIT
1 IM 5MSY-1009(1)_EN.indd 06
1 IM 5MSY-1009(1)_EN.indd 06
All manuals and user guides at all-guides.com
REFRIGERANT PIPING
Single Indoor
Maximum
Piping Length
(m)
+ L
≤ 50
L ≤ 25
2
+ L
+ L
≤
L ≤ 25
2
3
60
+ L
+ L
L ≤ 25
2
3
4
≤ 60
OUTDOOR UNIT
Maximum
Pre-charged
height
Total Piping
Difference (m)
length (m)
H ≤ 15
10
H ≤ 15
20
H ≤ 15
20
1-6
Outdoor Unit
Amount of
Pre-charged
Additional
(kg)
Charge (g/m)
2.0
20
2.6
20
2.6
20
VERTICAL HEIGHT
DIFFERENCE MAX. H
1/7/10 3:57:17 PM
1/7/10 3:57:17 PM