KL710A, KL731A, and KL735A Addressable
Point Detectors Installation Sheet
EN ES FR
IT
NL PL PT TR
1
3
EN: Installation instructions
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
CEN/TS 54-14 standard and local regulations.
To install a detector
1.
Insert the detector head into the mounting base and rotate
it clockwise until it clicks into place (Figure 1).
2.
The detector may be locked into the mounting base if
required. To do this, remove the locking tab before
installation (Figure 2).
© 2020 UTC Fire & Security. All rights reserved.
2
3.
After installation, ensure that the detector communicates
with the control panel. If the detector does not
communicate with the control panel, check that duplicate
addresses have not been assigned.
4.
Always test detectors after installation.
To remove a locked detector
1.
Insert a small screwdriver into the locking tab slot
(Figure 3).
2.
Press and rotate the detector anticlockwise.
Addressing
Each device requires a numeric address between 1 and 125
for identification purposes. This is assigned at the fire panel or
using a PG700N Device Programmer.
1 / 12
P/N 10-4221-501-KL7A-02 • ISS 05FEB20