Installation
on
1.
Turn off all power supplying this equipment
before working on or inside equipment.
2.
See Installation - Figure 1.
3.
Confirm M50 device is rated for your system
by comparing voltage measurements to the
Line Voltage on the product label.
4.
Install in accordance with article 285 of the
National Electric Code.
5.
Confirm that the electrical terminals used to
attach this device are identified for these
conductors.
6.
Twist conductors 1/2 turn or more for every 12
inches of length.
7.
Keep conductor length as short as possible
with no sharp bends.
8.
Do not loop or coil wires.
9.
Ensure a high quality ground is in place.
LED OFF (one or more) = Fault, check phase
Audible Alarm ON = Fault, check phase
Technical Data
2000 m max.
6500 ft max.
-40/+185°C max.
-40/+85°F max.
IP66
Characteristics
Single phase
Split phase
Wye
Delta
Max. Discharge
Current by mode (Imax)
Nominal Discharge
Current by mode
(In)
MCOV L-N (Vac)
MCOV L-L (Vac)
* M50F : contains a condenser.
Note:
A: for the side nipple
B: for the nipple in the back
Version B
Green/Yellow wire
Line wires
White wire
GND
Green/Yellow wire
N
L1
L2
L3
White wire
Line wires
*To avoid faceplate damage, DO NOT remove protective cover until after installed to surface mount.
P/N
50 kA
20 kA
Version A
88 mm
20.8 mm
.82 in
3.46 in
Optional Surface Mount Installation*
Installation (Fig. 1)
Fusing not required but only recommended when SPD installed
according to UL 1449.
N
L1
L2
L3
GND
Maintenance
: 3 LED ON = system protected
62 mm
2.44 in
: 1, 2 or 3 LED OFF = system unprotected
Main switchboard
or sub-panel
F1
and replace
by M50-xxxx-A
or M50-xxxx-B
U100201A

Publicidad

loading

Resumen de contenidos para Citel M50-120Y-A Serie

  • Página 1 Technical Data Installation (Fig. 1) Fusing not required but only recommended when SPD installed 2000 m max. according to UL 1449. INSTALLATION INSTRUCTIONS - NOTICE D'INSTALLATION 6500 ft max. NOTICIA DE INSTALACIÓN - INSTALLATIONSHINWEISE -40/+185°C max. ISTRUZIONI PER L'INSTALLAZIONE -40/+85°F max. Main switchboard INSTRUCOES DE INSTALACAO - MONTÁŽNÍ...
  • Página 2 - Svodič přepětí se smí používat pouze v souladu se svými technickými parametry a podle těchto www.citel2cp.com - 请根据不同的电源网络制式选用浪涌保护器,参见 montážních pokynů. Table ; www.citel.de - Svodiče přepětí je zapotřebí zvolit a používat tak, aby www.citel.us odpovídaly napájecí síti (viz tabulka). - 请在浪涌保护器前端安装规定的熔断器,参见 www.citel.com.cn - Potřeba instalace pojistek pro předjištění...

Este manual también es adecuado para:

M50-120t-a serieM50-120s-a serieM50-120y-b serieM50-120t-b serieM50-120s-b serieM50-240d-a serie ... Mostrar todo