Quick Start Guide
English
General features
TH 210-BXX models: 24 Vac/Vdc ±10%. TH 210-HXX models: 100-240 Vac, 50-60 Hz
Power supply
Output
Common mode voltage < 30 VAC. Maximum load: 500 Ω (0/4-20 mA). Minimum load: 10 kΩ (0-5/10 V)
Relay outputs
Galvanic isolation
Device fully protected by DOUBLE ISOLATION or REINFORCED ISOLATION
Consumption
Electrical connection
Screw terminal block for cable 2.5 mm². Executed following the good practices guidelines.
Type of sensor
Hygrometry: capacitive. Temperature: Pt100 1/3 as per IEC 60751 (2008)
Type of fluid
PC communication
Environment
Conditions of use
From -10 to 50 °C. In non-condensing condition. From 0 to 2000 m.
(°C/%RH/m)
Storage
temperature
Security
European directives
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Features of the housing
Material
ABS V0 as per UL94
Protection
IP65
75 x 40 mm, LCD 20 digits 2 lines.
Display
Height of digits:
Values: 10 mm; Units: 5 mm
Cable gland
For cables Ø 8 mm maximum
Weight
340 g
TH 210-R
Humidity and temperature transmitter
Stainless steel or
Two 4-wire analogue
polycarbonate
output 0-5/10 V or
0-5 / 10 V
4-20 mA
probes
0/4-20 mA
ABS V0 IP65 housing,
2 relay outputs
with or without display
Warning: risk of electric shock
2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
2 changeover relays. NO: 5 A/NC: 3 A/240 Vac
Inputs and outputs (models 100-240 Vac).
Outputs (models 24 Vac/Vdc)
TH 210-B: 6 VA/TH 210-H: 8 VA
Air and neutral gases
USB-Mini Din cable
Air and neutral gases
From -10 to 70 °C
Protection class II. Pollution degree 2. Overvoltage CAT II
All dimensions are in millimeters.
59
59
125
Ambient model
Remote model
Sortie analogique 1
(out 1)
Symbols used
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
Connections
Power supply type (b) speci ed on the label
Alimentation 24 Vac
classe II norme EN61558-2-6
on the side of the transmitter
230 Vac
Analogue output 1
(out 1)
Alimentation
24 Vdc
230 Vac
Alimentation 24 Vac
classe II norme EN61558-2-6
Pe
N
230 Vac
L
Electrical connections as per NFC15-100 standard
This connection must be made by a formed and qualified technician. To make the connection, the transmitter must not
be energized. Before making the connection, you must first check the power supply indicated on the transmitter board
Pe
(see (b) in "Connections" part). The presence of a switch and a circuit breaker upstream the device is compulsory
230 Vac
N
•
For transmitters with 24 Vdc power supply:
L
Alimentation
Alimentation
•
For transmitters with 24 Vac power supply:
100-240 Vac
24 Vac power supply
class II EN61558-2-6 standard
Tipo de alimentación (b) especi cada en la
230 Vac
etiqueta lateral del transmisor
Salida analógica 1
230 Vac
(Out 1)
24 Vdc
Power supply
125
•
For transmitters with 100-240 Vac power supply:
24 Vac power supply
class II EN61558-2-6 standard
Pe
N
230 Vac
L
Power supply
On 100-240 Vac models, if a fuse protection is used for the power line, it is imperative to use delayed-action
fuses in order to absorb the surge of current when first turned on the transmitter.
Pe
230 Vac
N
L
Power supply
100-240 Vac
(a)
(c)
ou
(c)
ou
Sortie analogique 2
Pour les modèles en
Pour les modèles en
Pour les modèles en
(out 2)
alimentation 24 Vdc
alimentation 24 Vac
alimentation 100-240 Vac
-
Neutre (N)~
+
Phase (L)~
NO : normalement ouvert
COM : commun
Relais 1 et 2
NC : normalement fermé
*Fusible uniquement présent sur les modèles 100-240 Vac.
Tout changement de fusible doit être réalisé appareil hors tension en utilisant un fusible TR5 630 mA 250 V.
5
1
4
3
6
2
-
0-5/10 V
0/4-20 mA
N-
Alimentation
-
+
-
24 Vdc
L+
N-
+
Alimentation
24 Vdc
L+
+
7
Alimentation 24 Vac
classe II norme EN61558-2-6
A
TH210-HOX-R
TH210-HOX-R
Power supply: 100-240 Vac
Power supply: 24 Vac/Vdc ±10 %
N
Af cheur régulateur ou
N-
50-60 Hz 8 VA
50-60 Hz 6 VA
Pe
Output: 0/4...20 mA / 0...5/10 V
Output: 0/4...20 mA / 0...5/10 V
automate type passif
N
N
N-
100-240 Vac
24 Vac/Vdc
230 Vac
L
L+
Pe
L
N
(a)
Sortie 4-20 mA
L+
L
(c)
or
(c)
or
L
ou
Analogue output 2
For 24 Vdc power
For 24 Vac power
For 100-240 Vac power
ou
(out 2)
supply models
supply models
0-5/10 V
0/4-20 mA
supply models
Pe
-
+
N
0-5/10 V
0/4-20 mA
-
N-
Pe
N-
230 Vac
N
+
-
-
Neutral (N)~
N
N-
+
Phase (L)~
N
L+
L+
L
L
+
Alimentation
L+
L
L
Alimentation
NO: normally opened
A
COM: common
Relays 1 and 2
Af cheur régulateur ou
NC: normally closed
V
automate type passif
Af cheur régulateur ou
N
N
N-
automate type passif
N-
*Fuse present only for 100-240 Vac models.
Alimentation
N
Every fuse replacement must be performed with a power off device using a TR5 630 mA 250 V fuse.
N-
Sortie 4-20 mA
100-240 Vac
L+
Alimentation
L+
L
Sortie 0-10 V
L
100-240 Vac
L+
L
PLC/BMS de tipo pasivo
ou
0-5/10 V
0/4-20 mA
-
+
N
N-
L+
The selection of the output signal in voltage (0-10 V or 0-5 V) or in current
L
5
1
4
0-5/10 V
0/4-20 mA
(4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board
-
-
+
3
N-
V
-
of the transmitter: put the on-of switches as shown in the table below:
24 Vdc
6
N-
Af cheur régulateur ou
24 Vdc
Power supply
L+
automate type passif
Power supply
2
+
L+
N
Configurations
4-20 mA
+
N-
Sortie 0-10 V
L+
24 Vac power supply
A
L
PLC/BMS de tipo pasivo
class II EN61558-2-6 standard
Regulator display or
Combinations
7
N
PLC/BMS passive type
N-
N
Pe
1 2 3 4
1 2 3 4
N-
Pe
N
N
TH210-HXXX-R
TH210-BXXX-R
230 Vac
L
L+
4-20 mA output
L
L+
Alimentación: 100-240 VAC
Alimentación: 24 VAC/VDC ±10 %
L
50-60 Hz, 8 VA
50-60 Hz 6 VA
L
•
Connection of the output in current
Salidas: 0/4...20 mA / 0...5/10 V
Salida: 0/4...20 mA / 0...5/10 V
or
4-20 mA:
100-240 Vac
24 Vac/Vdc
or
(a)
0-5/10 V
0/4-20 mA
0-5/10 V
0/4-20 mA
(c)
o
(c)
o
Pe
-
+
Pe
-
+
N
-
Salida analógica 2
N
Alimentación a
Alimentación a
Alimentación
N-
N-
230 Vac
N
N-
N
(Out 2)
24 Vdc
24 Vac
100-240 Vac
L
L+
L+
L
L+
+
L
L
Power supply
Power supply
-
Neutro (N)~
+
Fase (L)~
A
V
Regulator display or
Regulator display or
PLC/BMS passive type
PLC/BMS passive type
NO: Normalmente abierto
N
N
N
N-
COM: común
N-
Relés 1 y 2
N-
100-240 Vac
100-240 Vac
NC: normalmente cerrado
4-20 mA output
0-10 V output
Power supply
L+
L+
L+
L
L
L
*Fusible solo en modelos con alimentación 100-240 Vac
El remplazo del fusible debe ser efectuado con el dispositivo con la alimentación desconectada usando un fusible TR5 630 mA 250 V .
or
0-5/10 V
0/4-20 mA
-
+
N
0-5/10 V
0/4-20 mA
N-
-
+
-
-
L+
N-
N-
Fuente
L
Fuente
24 Vdc
L+
24 Vdc
L+
+
+
V
(c)
Terre fonctionnelle
Neutre (N)~
Phase (L)~
1. DIP switch (d)
2. LCC-S software connection
3. Relays
4. Analogue outputs (a)
0-5/10 V
0/4-20 mA
-
+
5. F3.20* fuse
6. Power supply terminal block (c)
7. Cable glands
A
Af cheur régulateur ou
automate type passif
Sortie 4-20 mA
(c)
0-5/10 V
0/4-20 mA
+
-
Operational grounding
Neutral (N)~
Phase (L)~
V
Af cheur régulateur ou
automate type passif
Sortie 0-10 V
PLC/BMS de tipo pasivo
0-5/10 V
0/4-20 mA
-
+
0-10 V
0-5 V
0-20 mA
A
Regulator display or
PLC/BMS passive type
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
4-20 mA output
•
Connection of output in voltage
0-10 V:
0-5/10 V
0/4-20 mA
(c)
+
-
Toma a tierra
Neutro (N)~
Fase (L)~
V
Regulator display or
PLC/BMS passive type
0-10 V output
0-5/10 V
0/4-20 mA
-
+