1.3 Address parameter list
Register address
1.3.1 Mode setting value register correspondence table
1.3.2 Fault information register correspondence table
1.4 Communication interface wiring
Please connect product communication interface A to RS485 converter communication interface A; B to RS485 converter
communication interface B; be sure to pay attention
to the A and B wiring when wiring, otherwise it will not be able to communicate normally. ﹙G is the communication cable shield
terminal block, can be connected or not﹚.
Data content
0000
Battery voltage
0001
Output voltage
0002
Output current
0003
Output frequency
0004
Restart delay value
0005
Low voltage protection value
0006
Low voltage recovery value
0007
Over voltage protection value Register high + register low
0008
Over voltage recovery value
0009
Overload ratio value
0010
Mode setting value
0011
Fault information
Bit
15
14
13
Name
Reserved
Bit
Detail
0-1
Reserved
MODE0: Overload short circuit mode
2
0: Automatic restart 1: Lock no output, need to restart
MODE1: Alarm sound mode
3
0: Early warning/fault sound 1: Silent
4-15
Reserved
Bit
15
14
13 ......
Name
Reserved
Bit
Detail
FAULT0: Battery over voltage error
0-1
00: Normal
01: Low voltage 10: Over voltage
FAULT1: Over temperature error
01: Front-end circuit over temperature
2-3
10: Back-end circuit over temperature
11: Both front and backend over temperature
4-5
Reserved
FAULT3: Output error
6-7
00: Normal
01: Over load 10: Shirt circuit
8-15
Reserved
Data description
(Register high + register low)/10
Register high + register low
(Register high + register low)/10
Register high + register low
Register high + register low
Register high + register low
Register high + register low
Register high + register low
Register high + register low
See the mode setting table for details
See the fault information table for
details
......
5
4
3
MODE1 MODE0
9
8
7
6
5
4
FAULT2
Reserved
00: Normal
- 18 -
Type
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2
1
0
Reserved
3
2
1
0
FAULT1
FAULT0

Publicidad