Installation Instructions - Push-In Wire Connectors
Models 32, 33, 34, 87, 88 & 90
• Do not exceed the rating of these connectors.
• Turn OFF power before removing or installing connectors.
• Wiring must comply with all applicable electrical regulations.
• COPPER TO COPPER ONLY. Do not use on aluminium wire.
• Incorrect use of these connectors can cause electrical fires, personal injury or death.
• These connectors are suitable for solid and semi-rigid (<7 strands) conductors.
They are not suitable or rated for use with flexible cable with >7 strands.
• Strip wires back 13mm.
• Grip wire firmly and push conductor into open port.
• Use only one conductor per port.
• Connectors are reusable on solid wires of the same wire gauge or larger.
If reusing connectors, cut and re-strip conductors.
• In order to remove a wire, pull and twist the wire back and forth.
• DO NOT RE-USE connector on stranded wire.
Strip Length
13mm
Specifications
Rating
Depth
Width
Height
Wire
Solid wire
Combination
Stranded wire*
Range
* Stranded wire is limited to ≤ 7 strand
Insertion
Model 32 Red
Model 33 Orange
2-Port
3-Port
32 Amp / 450V / 105°C maximum
19.81 mm
13.21 mm
17.53 mm
9.65 mm
0.75mm
to 4.0mm
2
1.5mm
to 2.5mm
2
www.idealind.com
Removal
Model 34 Yellow
Model 87 Grey
4-Port
5-Port
18.52 mm
20.83 mm
23.03 mm
9.02 mm
2
2
Removal
Model 88 Blue
6-Port
24 Amp / 450V / 105°C maximum
18.52 mm
15.32 mm
15.42 mm
0.75mm
to 4.0mm
2
2
1.5mm
to 2.5mm
2
2
Model 90
Black
8-Port
18.21 mm
35.03 mm
9.02 mm
1/5