Essential information
Programming pages
The following table shows which programming pages are available for each application, according to the model.
Page
Cng PASS
APPLiCAt
User
SELECtor
SYS
Ut rAtio
Ct rAtio
P int.ti
diG in
FiLtEr.S
FiLtEr.Co
AddrESS
Dig Out 1
Dig Out 2
Ene t.rES
End
Tariff management (IS model)
Managing tariffs via Modbus command
Change the tariff by entering the value corresponding to the current tariff according to the following table in the 1127h registry (04h or 06h
Modbus function):
Current
Register
tariff
value
T1
005Ah (90d)
T2
015Ah (346d)
T3
025Ah (602d)
T4
035Ah (858d)
Note: Modbus tariffs management is disabled by writing 0 in register 1127h.
Managing tariffs via digital inputs
1. Set diG in 1 and diG in 2 as "tAr".
2. Change tariff by changing input status according to the table below:
Current
input 1
tariff
T1
ON
T2
OFF
T3
ON
T4
OFF
Note: the tariff management is not available in SFA models
16
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
All manuals and user guides at all-guides.com
Application
A
B
x
x
x
x
-
-
-
x
x
x
x
x
x
x
x
x
-
x
-
-
-
-
x
x
x
x
x
x
x
x
x
x
input 2
ON
ON
OFF
OFF
C
D
E
x
x
x
x
x
x
-
x
-
x
-
x
x
-
x
x
x
x
x
x
x
x
-
x
-
x
x
-
-
-
-
-
-
x
x
x
x
-
x
x
-
x
x
x
x
x
x
x
The tariff management is not available in SFA models
F
G
H
x
x
x
x
x
x
-
-
-
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x