Communication
Power supply
Auxiliary power supply
Bus cable
Bus current consumption
Command elements
Display elements
Actuation elements
Maximum switchover current
Maximum power for load type
Maximum dissipated power
Ambit of use
Operating temperature
Storage temperature
Relative humidity
Bus connection
Electrical connections
Protection ratings
Dimension
Reference standard
Certifications

TECHNICAL DATA

KNX Bus
via the KNX bus, 29 V dc SELV
230Vac
KNX TP1
10 mA max
1 miniature programming key
4 push-buttons for local relay command
1 red programming LED
4 green LEDs for signalling output status
4 16AX relays with NO potential free contact
16 A (AC1)
16AX (140 µF ref. EN 60669-1) fluorescent loads
with maximum surge current 400A (200 µs)
Incandescent lamps (230 Vac): 3000W
Halogen lamps (230Vac): 3000W
Loads controlled by toroidal transformers: 3000W
Loads controlled by electronic transformers: 2000W
Low consumption lamps
(compact fluorescent lamps): 80x23W
5W
Indoors, dry places
-5 to +45 °C
-25 to +70 °C
Max 93% (non condensative)
Coupling terminal, 2 pins Ø 1 mm
Extractable screw terminals, maximum cable
section: 4mm
IP20
4 DIN modules
Low voltage directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC, EN50428, EN50090-2-2