MCS-B 1-100-240/12-15
Art. No. 85372
OPERATING INSTRUCTIONS
product of the
series
1
+
2
-
3
L
4
N
38
38
76
38
AC230V
L
N
Art. Nr. 85372
L
N
9
Art. Nr. 85372
IND.CONT.EQ.
E222272
1VD7
(1) General
This unit employs many features previously unavailable in an industrial power supply. It
has been designed to withstand the high levels of interference found in heavy industry and
has emission levels low enough for it to be used in residential, commercial and light
industrial environments.
The MCS-B 1-100-240/12-15 has a high level of reserve power. This enables loads with
significant inrush current to be supported and will also ensure that circuit breakers will trip
in event of short circuit.
A protective feature is provided which will take control as the unit approaches the power
limit due the overload or excessive temperature brought about by lack of ventilation.
This equipment shall be connected directly to the d.c. supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the d.c.
supply system earthing electrode is connected.
In order to take the best advantage of the
features that this power supply has to offer
and to ensure long term reliability for your
equipment, please read these instructions
carefully before installation and use. They
should be retained for future reference.
5
TA
6
7
15
12
9
6
2
3
0,4
0,8
1,2
Uout = 12 VDC
Uout = 15 VDC
1.2
1.0
0.8
(DC 12V)
0.6
0.4
0.2
(DC +/- 24 V)
(2) Technical specification, Art. No. 85372
Nominal voltage
Input voltage range
Input current, I
nom.
Inrush current
Efficiency, typ.
Power factor, typ.
Internal fuse F1:
Maximum rated Branch Circuit Breaker 10 A
Safety class
Output voltage, adjustable 12 - 15 VDC
Static regulation accuracy
Dynamic regulation accuracy typ.
Start-up time, typ.
Hold up time of the output, typ.
Output current, continuous
Output current, continuous
Output current, short circuit , max. 200 ms
Output ripple
Overloading / temperature protection
Relative humidity
Operation temperature
Storage temperature
Protection class, case, EN 60529
Dimensions W x H x D x TA; Weight
(3) Features
[1] Output terminal:
Conductor sizes
Solid
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded with ferrule without / with plastic sleeve
Ferrule minimum lenght must be
8
Tightening torque:
[2] Output voltage "OK", indicator light
[3] Output voltage adjust, 12 - 15 VDC
[4] Input terminal:
Conductor sizes
Solid
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded with ferrule without / with plastic sleeve
Ferrule minimum lenght must be
Tightening torque:
(4) Location
The power supply is cooled by natural convection. It is important to maintain clearance
to other components as much as possible to ensure best performance and long term
stability. Top and bottom clearances should be 50 mm at minimum. Side clearance to
1,6
other equipment should be 20 mm or > 50 mm if that equipment is heat generating. The
ambient temperature should be measured on the underside of the unit. There will be
an increase of 25°C at the top. If natural convection is restricted, forced cooling should
be used. Mounting should comply with EN 60950-1 point 4.7 and 4.6.1. Protection class
of the case IP20 (EN 60529).
(5) Mounting [7]
The rail should be fixed solidly so that it cannot twist when mounting or removing the
10
unit. Mounting instructions [5], Removing instructions [6].
(6) Switching on
Factory set, ready to use, check the connection diagram for series connection.
(7) Loading capacity
The nominal current is 1 A but due to the nature of industrial loading, the power supply
has been designed to support loads with high inrush currents without damage or
shutdown. Curve [8] shows the typical current / voltage curve, decreasing parts of the
curve shows the current limitation. Curve [10] show the current / temperature limits.
(8) Series connection
Up to 2 units may be connected in series to give either 24 VDC or +/-12 VDC. Check
the connection diagram [9].
(9) Using circuit breakers on the power supply output:
On the short circuit, the power supply will trip, for example, the following ABB-STOTZ
circuit breaker:
(10) Standards
Electrical safety
EMC
Immunity
Emissions
We reserve the right to change this specification.
100 - 240 VAC 50/60 Hz
90-265 VAC 50/60Hz, 110-300 VDC
0,29 A
/ 115 VAC - 0,16 A
rms
< 20 A / 230 VAC after 1ms
77% / 115 VAC - 76% / 230 VAC
0,54 / 115 VAC - 0,43 / 230 VAC
(UL listed Bussmann Typ. AGC-10A oder
Littelfuse No. 314 010) oder ABB S201-B10A
0->100%, 5% 1ms / 100%->5%, 5% 1ms
> 20 ms / 115 VAC - > 150 ms / 230 VAC
12 VDC / 1 A (+60°C)
15 VDC / 1 A (+50°C) - 0,8 A (+60°C)
5 - 95%, no condensing
38 x 76 x 80 x 7,5 mm; 0,13 kg
0,4 - 0,5 Nm / 5 - 7 lb. in.
0,4 - 0,5 Nm / 5 - 7 lb. in.
S201-Z0,5A
EN 60950-1, SELV
EN 61204-3 (2000), (EMI:class B, EMS:industry class)
EN 61000-4-2 (1995) ESD 4/8 kV
EN 61000-4-3 (1996) Rf-field 10 V/m
EN 61000-4-4 (1995) EFT/B 2/2 kV
EN 61000-4-5 (1995), Surge 1/2 kV; 500 V
EN 61000-4-6 (1996) Cond. Rf 10 V
EN 61000-4-11
ENV 50204 (1995) Rf-field 10 V/m
EN 55022 B, RF-emissions
EN 61000-3-2, class A
EN 60204-1, 60 V / 1 s
V1.1
/ 230 VAC
rms
T 1,25 A H 250 V
1
12 VDC
+/- 1%
0,7 s
> 6 A / 230V
< 50 mV
rms
Yes
0°C - +50°C
-25°C - +85°C
IP20
1,5 mm² / 16 AWG
≥
10 mm
1,5 mm² / 16 AWG
≥
10 mm