Confirming Supplied Accessories; Dimensions And Required Servicing Space Of Branch Box - Mitsubishi Electric PAC-MKA52BC Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Confirming supplied accessories

8
5
4
3
7
1
2
9
Fig. 3-1

4. Dimensions and required servicing space of Branch Box

Optional different-diameter (deformed) joints
A
Fig. 4-1
Connected pipes diameter
Model name
inch, mm
MAC-A454JP-E
3/8, ø9.52 → 1/2, ø12.7
MAC-A455JP-E
1/2, ø12.7 → 3/8, ø9.52
MAC-A456JP-E
1/2, ø12.7 → 5/8, ø15.88
PAC-493PI
1/4, ø6.35 → 3/8, ø9.52
PAC-SG76RJ-E
3/8, ø9.52 → 5/8, ø15.88
PAC-SG75RJ-E
5/8, ø15.88 → 3/4, ø19.05
PAC-MKA52BC (5-branches type)
17-23/32
3-17/32
2-27/32
2-9/16
E
D
C
B
A
E
D
C
B
A
1
1
1
1
1
2-3/4
2-3/4 2-3/4 2-3/4
B
Diameter A
Diameter B
inch, mm
inch, mm
3/8, ø9.52
1/2, ø12.7
1/2, ø12.7
3/8, ø9.52
1/2, ø12.7
5/8, ø15.88
1/4, ø6.35
3/8, ø9.52
3/8, ø9.52
5/8, ø15.88
5/8, ø15.88
3/4, ø19.05
(inch)
A
12-19/32
B
1/2
C
3-25/32
11-1/32
1-17/32
3-9/32
3-7/16 2-3/4
F
E
D
Fig. 4-2
3.1. Check the Branch Box accessories and parts
No.
Accessory name
Washer
1
(with insulation)
Washer
2
6
Pipe cover (Liquid)
3
Pipe cover (Gas)
4
Pipe cover (Liquid)
5
Pipe cover (Gas)
6
Joint cover (Liquid)
7
Joint cover (Gas)
8
Band
9
Conduit plate
0
* Please connect 2 indoor units or more with 1 system.
* Up to 2 branch boxes may be connected to 1 outdoor unit.
* Suspension bolt : W3/8 (M10)
* Refrigerant pipe flared connection
* The piping connection size differs according to the type and capacity of
indoor units. Match the piping connection size for indoor unit and branch
box. If the piping connection size of branch box does not match the pip-
ing connection size of indoor unit, use optional different-diameter (de-
formed) joints to the branch box side. (Connect deformed joint directly to
the branch box side.)
A Suspension bolt pitch
B To indoor unit
C To outdoor unit
D Service panel
E Electric cover
F Conduit plate
G Terminal block (to indoor unit on control board)
H Terminal block (to outdoor unit)
J Terminal block (for comunication cable)
PAC-MKA52BC (Fig. 4-2)
Suspension bolt: W3/8 (M10)
Refrigerant pipe flared connection
A
Liquid pipe 1/4, ø6.35 1/4, ø6.35 1/4, ø6.35 1/4, ø6.35 1/4, ø6.35
Gas pipe 3/8, ø9.52 3/8, ø9.52 3/8, ø9.52 3/8, ø9.52 1/2, ø12.7
J
G
H
Q'ty
PAC-
PAC-
MKA32BC
MKA52BC
4
4
4
4
1
1
To outdoor unit
1
1
To outdoor unit
3
5
To indoor units
3
5
To indoor units
1
3
1
3
16
24
Fastened to the main body
1
1
and shipped.
To indoor unit
B
C
D
E
Conversion formula
1/4 F
ø6.35
3/8 F
ø9.52
1/2 F
ø12.7
5/8 F
ø15.88
3/4 F
ø19.05
Remarks
inch, mm
To outdoor unit
3/8, ø9.52
5/8, ø15.88
en
2

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Pac-mka32bc

Tabla de contenido