Victron energy EasySolar-II 48/3000/35-32 230V MPPT 250/70 GX Manual De Instrucciones página 18

Ocultar thumbs Ver también para EasySolar-II 48/3000/35-32 230V MPPT 250/70 GX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 79
The battery is overcharged.
The charging current drops to 0 as soon
as the absorption phase initiates.
11.2 VE.Bus error codes
A VE.Bus system can display various error codes. These codes are displayed on the front GX display screen.
To interpret a VE.Bus error code correctly, you should refer to the VE.Bus error codes documentation -
https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes.
Code
Meaning:
Device is switched off because one of the other
1
phases in the system has switched off.
Not all, or more than, the expected devices were
3
found in the system.
4
No other device whatsoever detected.
5
Overvoltage on AC-out.
10
System time synchronisation problem occurred.
14
Device cannot transmit data.
One of the devices has assumed 'master' status
17
because the original master failed.
18
Overvoltage has occurred.
22
This device cannot function as 'slave'.
24
Switch-over system protection initiated.
Firmware incompatibility. The firmware of one the
25
connected devices is not sufficiently up to date to
operate in conjunction with this device.
26
Internal error.
16
an extremely high charging current with
respect to battery capacity, so that bulk
time is insufficient.
The absorption voltage is set to an
incorrect level (too high).
The float voltage is set to an incorrect
level (too high).
Poor battery condition.
The battery temperature is too high (due
to poor ventilation, excessively high
environmental temperature, or
excessively high charging current).
Defective battery temperature sensor
The battery is over-heated (+50°C)
Cause/solution:
Check the failing phase.
The system is not properly configured. Reconfigure the
system. If the error persists, possible communication cable
error. Check the cables and switch all equipment off, and then
on again.
Check the communication cables.
Check the AC cables.
Should not occur in correctly installed equipment. Check the
communication cables.
Check the communication cables (there may be a short
circuit).
Check the failing unit. Check the communication cables.
Check AC cables.
This device is an obsolete and unsuitable model. It should be
replaced.
Should not occur in correctly installed equipment. Switch all
equipment off, and then on again. If the problem recurs,
check the installation. Possible solution: increase lower limit
of AC input voltage to 210 VAC (factory setting is 180 VAC)
1) Switch all equipment off. 2) Switch the device returning
this error message on. 3) Switch on all other devices one by
one until the error message reoccurs. 4) Update the firmware
in the last device that was switched on.
Should not occur. Switch all equipment off, and then on
again. Contact Victron Energy if the problem persists.
Set the absorption voltage to the correct
level.
Set the float voltage to the correct level.
Replace the battery.
Improve ventilation, install batteries in a
cooler environment, reduce the charging
current, and connect the temperature
sensor.
Disconnect the temperature sensor plug
in the EasySolar-II GX. If charging
functions correctly after approximately 1
minute, the temperature sensor should
be replaced.
Install the battery in a cooler
environment
Reduce the charging current
Check whether one of the battery cells
has an internal short circuit

Publicidad

Tabla de contenido
loading

Tabla de contenido