DATOS TÉCNICOS
GENERAL DATA
Max Voltage (U
)
N
Max Input short-circuit Current (I
Max Output short-circuit Current (I
MECHANICAL DATA
Housing
Housing Dimensions (W x D x H in mm)
Weight
Degree of Protection
Protection Class
Color (RAL)
ENVIRONMENT DATA
Ambient Temperature Normal Operation
Ambient Temperature Storage
Humidity
Altitude
DC INPUT DATA
Number Strings
Sealing range cable entry (per input)
Input Cable Glands entry (per pole)
Input Connection
Conductor cross section
Fuse Holder
Fuse Type
Fuse Size
DC OUTPUT DATA
Output Cable Glands
Clamping Area
Conductor Material
Terminal Type
Switch Type
SPD Protection
1
Derating of U
according to altitude. Reduction of 1% per 100m from 2001m to 3000m and 1.2% per 100m from
N
3001m to 4000m.
2
Derating of 1%/K of max current from 50°C to 60°C.
3
Optional on request SPD Type I + II 20kA/40kA.
Cod: 910.400.216SP REV00
TECHNICAL DATA STRING BOX SB20 @ 1500Vdc
)
scSTC
)
scSTC
DC 1500V
GRP (Glass Fiber Reinforced Polyester)
550 x 300 x 650
IP 65 (outdoor installation)
CLASS II
RAL 7035
-25 °C ... 60 °C
-40 °C ... 70 °C
0 % ... 95 % (not - condensing)
up to 4000m
5 ... 8 mm
Nr. 5 PG32 with 4 input each one
Directly on Fuse Holder
4 ... 6 mm
DIN Rail Mounting - 1 pole - 1500Vdc
10.3 x 85 - 1500Vdc - gPV
Available 6 ... 20 A – installed 15A
Nr. 2 M50x1,5 per pole
Up to 38 mm
Copper
Copper bus-bar with M12 screw
Under Load Switch-Disconnector - 3 pole - 1500Vdc
SPD Type II 20kA/40kA
1
15 A
355 A
29 kg
2
20
2
3
Pág. 11 / 24