Huber Power 812 Serie Manual De Usuario página 27

Tabla de contenido

Publicidad

Table 2 En modo Inversor
INVERTER MODEL
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Efficiency
Overload Protection
Surge Capacity
Nominal DC Input Voltage
Cold Start Voltage
Low DC Warning Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Warning Return Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
High DC Recovery Voltage
High DC Cut-off Voltage
No Load Power Consumption
Saving Mode Power Consumption
1KVA
1KVA/0.8KW
2KVA/1.6KW
Pure Sine Wave
230Vac±15%
5s@≥150% load; 10s@110%~150% load
2* rated power for 5 seconds
12Vdc
11.5Vdc
11.0Vdc
10.7Vdc
10.1Vdc
12.5Vdc
11.2Vdc
10.6Vdc
10.5Vdc
10.2Vdc
9.6Vdc
14Vdc
15Vdc
<15W
<5W
26
2KVA
3KVA
3KVA/2.4KW
50Hz
>90%
24Vdc
23.0Vdc
22.0Vdc
21.4Vdc
20.2Vdc
23.0Vdc
22.4Vdc
21.2Vdc
21.0Vdc
20.4Vdc
19.2Vdc
29Vdc
30Vdc
<20W
<10W