CABLE ROUTING RECOMMENDATIONS / RECOMMANDATIONS DE CHEMINEMENT DES CÂBLES /
RECOMENDACIONES DE RECORRIDO DE CABLES
USING ADAPTER STRIPS AND PIGTAILS / EN UTILISANT DES BANDES ADAPTATRICES ET DES CÂBLES D'AMORCE / UTILIZANDO BANDAS DE
ADAPTADORES Y COLETAS
Note: For drawing clarity, routing for one adapter strip only is shown.
Note: Pour la clarté du dessin, le cheminement pour une seule bande adaptatrice est illustré.
Nota: Por la claridad del dibujo, el recorrido de una banda de adaptadores solamente se muestra.
1
(ENGLISH)
1. Enter the cable in the panel as shown and route it around the plastic spools for at least one turn.
2. Fix the cable to the splice tray using a cable tie (K)
3. Fix the cable to the slide-out tray using cable ties (K)
4. Route 900μm fibers in the splice tray for at least one turn. The recommended length from the breakout point
[64 to 74 cm].
5. The minimum recommended routing bend radius
6. Splice the fiber to the pigtails and secure in the splice holder. The recommended lengths of the pigtails (distance between the splice point
tip of the connector) are the following:
Adapters in position
&
6
Adapters in position
: 17 to 24 inches [43 to 61 cm]
8
7. Place the splice tray cover. Plug the fiber optic connectors in the adapters.
ISHT06_ART_B
6 / 7
5
6
1
.
K
K
2
.
is 1 inch [2.5 cm].
4
: 11 to 17 inches [28 to 43 cm]
7
2
3
7
4
8
to the tip of the fiber is 25 to 29 inches
3
and the
5