17.
Orient cover support collar [15] as required by removing and reinstalling screws [16]. Lap joint in collar defines the
hinge location of the cover, SEE FIGURES D & E.
18.
Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [15]. FOR CERAMIC TILE - DO NOT GROUT
BETWEEN THE SUPPORT COLLAR AND TILE.
19.
Adjust height of cover support collar flush to just below the finished floor. Cover support collar is adjustable for
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick. Tighten mounting screws [16] to 10 - 15 lbs-in torque
[1.1 - 1.7 N m]. For thicker floor finishes use accessory collars (CFB8RCVRRx), sold separately.
20.
Seal the gap around the cover support collar [15] with a continuous bead of electrical grade type RTV silicone sealant,
SEE FIGURE F.
21.
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical grade type RTV silicone
sealant around the perimeter on the underside of the flange [17].
22.
Attach flange [17] to the cover support collar [15] using #8-32 flat head screws [18] provided with the cover. Tighten
to 10 - 15 lbs-in torque [1.1 - 1.7 N m].
LAP JOINT
(HINGE SIDE)
16
15
LAP JOINT
(HINGE SIDE)
FIGURE
E
FIGURE
F
15
18
FIGURE
D
17
SEAL ALL AROUND
CFB4GS1R8ADAPT ROUND COVER ADAPTER FOR 4 GANG RECESSED
CONCRETE FLOOR BOX Installation Instructions
CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with all national and local electrical codes,
communications standards, the following instructions and any instructions included with individual devices.
NOTICE: Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC and
CE Code requirements.
Use with CFB4G25, CFB4G25CR, CFB4G30, CFB4G30CR, or CFB4G30CI floor boxes.
Use with CFBS1R8CVRxx series round covers.
BEFORE CONCRETE POUR, SEE FIGURES A & B
1.
Remove four #8-32 flat head screws [1] from top corners of floor box assembly and discard.
16
2.
Remove mounting plate [2] from the box.
3.
REMOVE AND DISCARD PLASTIC [3] AND METAL [4] COVERS ATTACHED TO THE MOUNTING PLATE [2].
4.
Install leveling screws [5] as shown in FIGURE A.
5.
Make conduit connections in accordance with application and applicable electric codes. For deep sheet metal
boxes (CFB4G30xx), 2" trade size conduit hubs, (CFBHUB2), sold separately, may be used in place of knockout
plates [6] as needed. For cast iron boxes, remove closure plugs [7] as needed. Unused conduit ports should
be left covered with closure plugs [7], SEE FIGURE B.
6
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2596
04/14
5
FIGURE
A
ENGLISH
3
4
1
2

Publicidad

loading

Resumen de contenidos para Hubbell CFB4GS1R8ADAPT

  • Página 1 CFB4GS1R8ADAPT ROUND COVER ADAPTER FOR 4 GANG RECESSED Orient cover support collar [15] as required by removing and reinstalling screws [16]. Lap joint in collar defines the hinge location of the cover, SEE FIGURES D & E. CONCRETE FLOOR BOX Installation Instructions Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [15].
  • Página 2 For feed-thru wiring, remove non-metallic dividers [8] as necessary. AFTER CONCRETE POUR, SEE FIGURES C, D, E, & F Reposition mounting plate [2] in floor box. Install adapter [9] on top of the mounting plate [2]. Secure using #8-32 Locate floor box, remove three screws [12] and remove temporary concrete cover [11]. CAUTION: Temporary pan head screws [10] supplied with adapter.
  • Página 3 Orienter le collier de soutien du couvercle [15] au besoin en retirant et en r installant les vis [16]. Le joint de DE B TON ENCASTR E 4 COMPARTIMENTS CFB4GS1R8ADAPT recouvrement du collier repr sente la partie charni re du couvercle (consulter les FIGURES D et E).
  • Página 4 Pour le c blage en travers e, enlever les cloisons non m talliques [8] au besoin. APR S LA COUL E DU B TON, CONSULTER LES FIGURES C, D, E ET F Repositionner la plaque de montage [2] dans la bo te de plancher. Monter l'adaptateur [9] par-dessus la plaque de Localiser la bo te de plancher, retirer les trois vis [12] et le couvercle temporaire [11].
  • Página 5 FIGURA Wiring Device - Kellems HUBBELL DE M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el Hubbell Incorporated (Delaware) art culo a su juicio en un plazo de 60 d as.
  • Página 6 Para cableado atravesado, retirar los divisores no met licos [8] seg n la necesidad. DESPU S DEL COLADO DEL HORMIG N, VER FIGURAS C, D, E, & F Volver a posicionar la placa de montaje [2] en la caja para piso. Instalar el adaptador [9] encima de la placa de Ubicar la caja para piso, retirar tres tornillos [12] y la tapa temporal para hormig n [11].