3 Location of the sensor ETS-05
• As indicated in the system design documentation
• Away from valves, flanges, supports, pumps, or other heat sinks
• At the top of the pipe for thermally sensitive pipe contents (A)
• On lower quadrant of pipe 90° for single heating cable (B)
• On lower quadrant of pipe centrally between the heating cables if they
are two or more (C)
4 Attachment of the sensor ETS-05
WARNING: Do not install sensor at ambient temperatures below
–20°C. Do not bend sensor (last 50 mm), keep it straight under all
circumstances. Minimum bending radius for High Temperature Mineral
Insulated Sensor extension cable is 20 mm.
1. Fix sensor firmly on surface with adequate fixing tape in two places (D)
2. Fix sensor parallel to pipe (D)
3. Route extension cable to avoid damage in use. Fix to pipe with
adequate tape where appropriate
8 | nVent.com/RAYCHEM
D
A
B
90°
C