List Of Parametrers - Saci pumps [e]motion Serie Manual De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
14 - LIST OF PARAMETERS
Par.
Description
1.1
PRESSURE SETPOINT
1.4
MOTOR CURRENT
1.5
ROTATION DIRECTION
1.6
STOP FREQUENCY
START-UP DIFFERENTIAL
1.7
Par.
Description
2.01
MODULE TEMPERATURE
2.02
ANALOGUE SIGNAL 1
2.03
ANALOGUE SIGNAL 2
2.04
0-10V INPUT
2.05
MOTOR THERMISTOR
2.06
VOLTAGE HOURS
2.07
HOURS WORKED
2.08
START-UP NUMBER
2.09
DIGITAL INPUT 1
2.10
DIGITAL INPUT 2
2.11
DIGITAL INPUT 3
DIGITAL INPUT 4
2.12
2.13
RELAY 1 OUTPUT
2.14
RELAY 2 OUTPUT
2.15
SOFTWARE VERSION
2.16
CONS. POWER OF PUMP
CONS. POWER OF GROUP
2.17
Programming
Units
Default
Min.
Bar
Wizard
0,5
Amp
Wizard
0,1
0
Hz
Wizard
0,1
Bar
0,5
0,3
Units
ºC
This indicates the temperature the electronic module of the inverter.
This indicates the value in mA of the pressure transducer 1.
mA
This data will be 4 mA for 0 Bar and 20 mA for the upper limit of the transducer connected.
This indicates the value in mA of the pressure transducer 2.
mA
This data will be 4 mA for 0 Bar and 20 mA for the upper limit of the transducer connected.
V
This indicates the value of the 0-10V signal if it is enabled in one of the inputs.
kohm
This indicates the value of the NTC/PTC signal if it is enabled on settings.
Hours
This indicates the total number of hours the inverter has been connected to an electricity grid.
Hours
This indicates the total number of hours worked (providing an output voltage) of the inverter.
This indicates the total number of start-ups from zero that the unit has made.
This indicates whether digital input 1 is ON or OFF.
This indicates whether digital input 2 is ON or OFF.
This indicates whether digital input 3 is ON or OFF.
This indicates whether digital input 4 is ON or OFF.
This indicates whether the relay 1 output is ON or OFF.
This indicates whether the relay 2 output is ON or OFF.
Version of the unit software.
W
Instantaneous power consumed in output terminals toward pump.
W
Power consumed instantaneously by all of the pumps.
1. PARAMETERS
Max.
FS
Pressure you wish to maintain in the system.
Current of the motor in amperes. Taking into account whether your motor is wired as
MT2-11A
three phase 230V or three phase 400V. Insert nominal value.
TT3-11A
TT3-30A
You can change the rotation direction of the motor by modifying this parameter from
1
0 to 1 or vice versa.
The system will stop when the Inverter has been working for a certain time (see
99,9
parameter 5.12) under this frequency.
This is the differential that enables you to reduce the pressure to start the pump using
3
the value entered in parameter 1.1.
2. DISPLAY
Notes
42
EN
Notes

Publicidad

Tabla de contenido
loading

Productos relacionados para Saci pumps [e]motion Serie

Este manual también es adecuado para:

[e]motion mt2-11aE]motion tt3-11a[e]motion tt3-30a

Tabla de contenido