ALARMS - Continued
ALARM TEXT
Stop Float Fail
Lead Float Fail
Off Float Fail
Enable Float Fail
Float Config Error
C-Level™ Error
Alarm 2
Alarm 3
Press Test/Silence to Reset Alarm
SJE Rhombus
®
DEFINITION
The controller has sensed that the
stop float has failed to close while
higher level float switches have closed
The controller has sensed that the lead
float has failed to close while the stop
and higher level float switches have
closed.
The controller has sensed that the
redundant off float has failed to close
while higher level float switches have
closed.
The controller has sensed that the
timer enable float has failed to close
while the redundant off and higher level
float switches have closed.
The controller has sensed a C-Level™
sensor signal connected to the field
wiring terminals, while configured as
float switch controlled.
The controller has sensed a signal
outside the normal operating range of
the C-Level™ sensor.
A contact closure has been sensed by
the Alarm 2 input circuit.
A contact closure has been sensed by
the fourth digital input circuit when
in Simplex Demand mode or Duplex
Demand 3-Float mode.
The controller is configured for manual
alarm reset and the formerly active
alarm is now inactive.
E13
FIX
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
• Ensure the controller is configured for
C-Level™ sensor.
• Ensure the controller is configured for
float switch control if a C-Level™
sensor is not used.
• Ensure the C-Level™ sensor is properly
connected to the controller.
• Ensure the C-Level™ sensor cable has
not been damaged.
• Check the system monitored by the
Alarm 2 input.
• Check the system monitored by the
fourth digital input.
• Press the Test/Silence button to reset
the alarm status.
Type IFS Operation Manual