TROUBLESHOOTING INFORMATION SCREENS

Current Panel Configuration
Duplex
Timed Dose
C-Level ™ Sensor
40" Sensor
This section displays the current configuration of the controller. *The example shows a controller
configured as a Duplex, Timed Dose using a 40" C-Level ™ sensor for level sensing.
C-Level™ Status
Simulator
Frequency
Tank Level
The simulator is used to verify the functionality of the controller by simulating the tank level.
This section displays the frequency of the C-Level ™ sensor as measured by the controller, as well
as the calculated tank level. The normal operating range of the C-Level ™ sensor is between 1000Hz
and 3000Hz. If the C-Level ™ sensor frequency is operating significantly outside of the normal range,
a "Sensor Fail" alarm will occur.
Float Status
Redundant High Level
Redundant Low Level
This screen displays the status of each float switch connected to the controller. *The example shows a
controller configured as C-Level™ sensor control.
Pump Status
Pump 1 Called
Pump 1 Amps
Pump 2 Called
Pump 2 Amps
This screen displays the status of each pump connected to the controller. *The example shows a
controller configured as Duplex.
Alert Status
Horn
Beacon
Alarm Aux
This screen displays the status of the controller alarm.
SJE Rhombus
®
2315 Hz
26.3 in
Down
Up
Off
0.0 A
Off
0.0 A
Off
Off
Off
E14