If the ironer is disconnected from the electricity supply, the discon-
nector must be lockable or the point of disconnection must be mon-
itored at all times.
If local regulations require the installation of a residual current device
(RCD), a type A residual current device can be used.
Vent ducting (only for models with exhaust fan)
 Risk of fire if vent ducting is not fitted correctly.
The vent ducting must not be channelled into a chimney or flue
which is already in use for any type of burning installation (gas, coal
or oil). The vent ducting for the ironer must be installed separately
from the vent ducting for any tumble dryers.
The warm and moist exhaust air from the ironer must be conducted
outdoors or to a suitable venting duct via the shortest possible path.
Suitable measures must be taken to prevent condensate from flowing
back into the ironer. If the fan is not powerful enough to remove the
moist air, a suitably powerful additional fan must be fitted in the shaft
or the roof outlet on site. There must be sufficient air intake to the in-
stallation site to match the air outlet volume.
- The connector for the vent ducting (optional for PRI 210) is located
on the rear of the left side column and has a diameter of 70 mm
(HT DN 70).
- The exhaust ducting must have an internal diameter of 70 mm
(HT DN 70).
- If the vent ducting is directed upwards, a condensate drain hole
with a diameter of approx. 3–5 mm must be provided at the lowest
point.
- Adequate ventilation of the installation room must be ensured.
- The on-site vent ducting and the exit point to the outdoors must be
checked on a regular basis for a build-up of lint. Clean them
whenever necessary.
- The end of the ducting leading outdoors must be protected against
the elements (e.g. with a downward-facing 90° elbow).
en - Installation and planning notes
13