Operation Instruction of H5000 Series Inverter
Error
Content
code
4-20mA broken 1: Loose terminal and
20
wire
Wrong
Pr
Parameters
Wrong
Err
Parameters
8-6 Remove Regular Error
(1) Parameter cannot be set
Reason and solution:
A: Lock the parameter, and set F1.18 for 0, and then set
other parameters.
B: Running machine communicates abnormally. Reinstall running
machine and check whether the connection line is broken down.
C: Machine is running, and parameter cannot be set. Please
stop the machine and set.
Press "run" (external control) but the motor does not run
(2) Reason and solution:
A: Wrong running mode, please check if F1.02 is set for 1.
B: Frequency order is not given or the frequency is below
the start frequency.
C: Peripheral connection mistake, please check
peripheral connection.
D: The definition of Inverter input terminal is wrong, and not match
peripheral connection. Check 3.15-F3.22 parameter.
E: Start button is fault and controlling wire is broken.
Check control wire and button.
F: Inverter is in protection and is not reset. Please reset
and restart.
Manual de Funcionamiento del variador de la serie H5000
Possible reason
bad connection
1.Parameters are set
wrong
1.The parameters are
not existent
230
Solution
1: Check connection line
and link the broken
down wire
1.Correct to set the
parameters
1.Quite the parameters