retelec H5000 Serie Manual De Usuario página 254

Tabla de contenido

Publicidad

Manual de Funcionamiento del variador de la serie H5000
Operation Instruction of H5000 Series Inverter
F6.01=0-------------------- ( negative feedback mode )
F6.02=0-------------------- ( figure targeted value )
F6.03=0-------------------- ( FIV as feedback value )
F6.20=2-------------------- ( KB1, KA1 )
F6.21=1-------------------- ( KB2, KA2 )
F6.22=4-------------------- ( KB3, KA3 )
F6.23=3-------------------- ( KB4, KA4 )
F6.24=6-------------------- ( KB5, KA5 )
F6.25=5-------------------- ( KB6, KA6 )
F6.41=2-------------------- ( pressure allowance of pump up )
F6.60=50------------------ ( targeted value according to actual condition )
F6.42=48HZ-------------- ( Running frequency of pump up )
F6.43=8S------------------ ( delay time of pump up )
F6.45=5-------------------- ( pressure allowance of pump down )
F6.46=25HZ-------------- ( running frequency of pump down )
F6.47=2-------------------- ( delay time of pump down )
F6.49=1-------------------- ( time of injection gate )
F6.50=1-------------------- ( time of pull gate )
F6.51=240min------------ ( circuit time )
F6.68=255----------------- ( sleep section mode )
F6.69=5-------------------- ( sleep pressure allowance )
F6.70=60------------------ ( sleep time )
F6.71=25------------------ ( sleep frequency )
F6.73=3-------------------- ( wake-up )
F6.74=3-------------------- ( wake-up time )
254

Publicidad

Tabla de contenido
loading

Tabla de contenido