Electrical Connection; Important - WPool WPS 60 Guía De Instalación Y Uso

Ocultar thumbs Ver también para WPS 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.2

Electrical connection

Important :

personnel. Check that the cable supplying the technical room has a sufficiently large cross-section
to support the additional consumption required by the machine.
The heat pump must be supplied from an independent D-curve circuit breaker which can be either on
the main electrical panel equipped with a differential or on an independent panel connected to the main panel,
which will have a differential. If this is not the case, add a differential to the independent panel of your heat pump.
Reference
WPS 60
WPS 80
WPS 100
WPS 120
Electrical connection on the terminal block of the heat pump
Monophase
Unscrew the handle to access the electrical connection
The connection of your heat pump must be carried out by authorised and qualified
D-Curve circuit
Power supply
breaker power
Monophase 230 V
16 Amperes
Monophase 230 V
20 Amperes
Monophase 230 V
25 Amperes
Monophase 230 V
25 Amperes
Cable section according to the distance
between the circuit breaker and the heat
pump.
- 10 m
10 -15 m
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
Three-phase
L :
Line
N :
Neutral
:
Earth
+ 15 m
3G6 mm2
3G6 mm2
3G6 mm2
3G6 mm2
44

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wps 80Wps 100Wps 120

Tabla de contenido