Salicru CS141 Manual Rápido página 7

Ocultar thumbs Ver también para CS141:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EN
CS141 SNMP / WEB / MODBUS MANAGER
Descrition
Function
1 COM-Port 1
Serial Interface to connect an UPS or another device with a original RS232 cable
2 COM-Port 2
Communication port to connect additional devices for for use with CS141 devices:
GSM Modem, temperature and humidity sensor, SENSORMANAGER_II, Fieldbus devices
(MODBUS RS232, Profibus, LONBus, etc.).
Available for CS141L, CS141SC, CS141MINI & CS141R_2 = RS232 Available at CS141LM & CS141SCM
=RS485 (not equipped CS141BL, CS141BSC)
3 LAN-Port
Ethernet 10/100 Mbit Interface with integrated status LEDs
Green LED: General connection indicator
Yellow LED: network traffic indicator
4 DC– Input
12 V switching power adapter input - only available for external CS141 devices
5 AUX
Additional Port for connection CON_R_AUX4 und BACS
Available for CS141L, CS141LM, CS141SC und CS141SCM devices
6 Status-LEDs
CS141 operating state
Unpacking and installing operating system during update
procedure
Unpacking failure during update procedure
Booting / powering up
Connections lost to external devices (UPS, Sensors, etc.)
Normal operation state—connection to all devices is OK
Toggle different boot conditions
7
Sliding switch
DIP Switch
Sliding switch in center position
address: The CS141 can only be reached via the hard-coded IP - Address 10.10.10.10. The
mode will be activated after a reboot, choose between software reboot and cold start.
Sliding switch to right position
CS141 will obtain an IP address via local network infrastruction devices. Please check the MA-
CAdress of the CS141 to find the valid IP address at your DHCP server
Sliding switch to left position
Please configure IP address data manually.
8 USB
The CS141 is more than a SNMP card, it is a full featured web manager with numerous options and provieds plenty of accessory
space: As an example, the CS141 can be combined with a variety of environmental sensors and other measuring devices to measure
and monitor temperature, humidity, fire and smoke, motion and burglary, air pressure, fill levels, etc. - it can even write alarm mails,
send SMS messages, tswitch and toggle devices or comunicate with other systems.
/
1 + 2 set to
OFF: Configuration mode with hard-coded IP
/
1 set to OFF + 2 set to
ON: Automatic DHCP-mode - The
/
1 set to ON + 2 set to
OFF: Manual IP address mode -
LED condition alert:
Red LED blinks
Red LED blinks fast
Red LED is on
Red and green LED static on
Green LED blinks
Version: 2021-01-25

Publicidad

Tabla de contenido
loading

Tabla de contenido