Elkron AS02/S Manual Del Usuario página 16

Ocultar thumbs Ver también para AS02/S:
Tabla de contenido

Publicidad

TERMINAL BLOCKS DESCRIPTION
Supporting terminals for wiring tampers, if any
TAMPER
Output of fuse failure warning (and/or battery low)
G
Open collector type , provides a negative in warning - max 2 mA
Output of battery low warning
BL
Open collector type , provides a negative in warning - max 2 mA
Output of mains presence warning
L
Open collector type , provides a negative in warning - max 2 mA
By supplying a negative on this terminal, the battery test function is armed.
CPS
This function is possible with the relevant power suppliers (PS515) and is useful
to check the buffer battery efficiency.
Power supply to devices. Protected by 1A fuses
POWER
Buffer battery connection
+BAT-
Connection to power supplier terminals (PS515)
- + C
PS515 Features
PS515 POWER SUPPLIER
The factory setting of voltage drop (14.5V adjustable) takes
account of the 0.6/0.7 V voltage drop at the edges of the
protection diode installed in many alarm control units and
in most ELKRON control units.
(((ELKRON)))
16
+ - C
FUSE
F - 3,15A
input 230V~

Publicidad

Tabla de contenido
loading

Productos relacionados para Elkron AS02/S

Este manual también es adecuado para:

As07/sAs15

Tabla de contenido