IL Area Controller with SCMA0401 Adaptive Dimmer
Typical connection diagram
Incoming Supply
120 - 277V AC
Mains supply protection:
Provided by installer (6A Type C MCB recommended)
L N
iCAN Network
Termination
Device LEDs and buttons
Status LED
Green LED flashes – device OK
Green LED flashes rapidly - device under DALI control
Data LED
Red LED flashes when messages sent on network
Red LED solid indicates iCANnet network error
Alarm LED
Red LED flashes ON for local initiated alarm
Red LED solid for network initiated alarm
Device Identification
Press and release switch.
Sending a message to identify the device on the network
(red Data LED flashes)
Warranties and Limitation of Liability
Please refer to www.cooperlighting.com for our terms and conditions.
Connection
Alarm Input
to the iCAN
(volt free)
Network*
* This unit does not output +V to the iCAN network. Requires 85mA @ 15V DC
either via pre-powered iCAN network or from external PSU
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
For service or technical assistance:
1-800-553-3879
LED
Lamps
DALI
Input
Channel Output Status LEDs
LEDs turn on when the channel is > 0%
LEDs turn off when the channel is 0%
Manual Control of Channel Outputs
By holding the IDENT button down for 5 seconds, manual control of each
channel is enabled using the UP and DOWN buttons.
A short press of the UP button will raise the output level by 10% on each
press. A long press (>1s) of the UP button will set the output level to
100%. The same operation is true for the DOWN but in reverse.
Press the IDENT button to change the output channel being controlled.
To exit manual control hold the IDENT button down for 5 seconds.
© 2022 Cooper Lighting Solutions
Canada Sales
All Rights Reserved.
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
Product availability, specifications,
P: 905-501-3000
and compliances are subject to
F: 905-501-3172
change without notice.
WaveLinx Wired
Manual Control
Buttons
Device Identification
Button
IMPORTANT NOTE: Connecting a mains potential cable to the
iCAN Network terminals is likley to damage the unit and other
devices connected, and invalidate warranty.
IB50301922 page 7