11 - TECHNICAL CHARACTERISTICS
Please follow the instructions on the CPY card configuration sheet provided with the unit.
11.2.4 - Condensate drain pump:
This option is only available if the humidifier option has not been requested.
Specifications:
- Electrical power supply: 230 V-50 Hz-90 W
- Max. flow rate: 500 l/h
- Max. discharge height: 5.4 m
- Integrated check valve
Table of actual flow rates for pump SI 1805
The pressure drops defined in this table
are calculated using 10 mm diameter
flexible piping
Connect a Ø 10 int (3/8") flexible tube (not supplied by CIAT) to the pump discharge.
For OVER models (3 and 5), if using a spreader beam and slings, the PVC tube will not be directly connected to the pump,
for handling reasons. It must therefore be angled in the right direction and fixed to the clamp, as shown below.
Condensate discharge
with check valve
Discharge
height
1 m
2 m
3 m
4 m
5 m
Total pipe length
5 m (l/h)
10 m (l/h)
460
380
390
320
300
250
200
180
90
80
EN-53
20 m (l/h)
30 m (l/h)
280
200
240
180
190
150
130
100
60
50
®
MAGISTER
EN