Digital input. Allows you to activate or deactivate this function and change:
•
Settings. Allows you to set the input as normally open or normally closed.
•
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
•
Activation by edge: the status is punctual, only the on/off is sent when the opening or
closing condition is met for the first time.
•
Time to turn off (minutes). Displays a drop-down for selecting the time (in minutes)
that you want to elapse before turning off the equipment after receiving the signal. If
disabled, the equipment will automatically turn off after receiving the signal.
•
Time to turn on (minutes). Allows you to select the time (in minutes) that must elapse
with the signal deactivated before the equipment turns on again. This setting only turns
on the equipment if it has previously been turned off. If it is disabled, the equipment
must be switched on again manually.
Smart thermostat*. In the case of having a connection with a smart thermostat, this allows you
to select if the control is carried out by the Airzone Cloud app or by the thermostat in the case
of not having a link or connection with the third-party account.
Auto Mode (dual setpoint). Allows you to configure changing from automatic mode based on
the setpoints defined for the cooling and heating mode. The configurable parameters are:
•
Setpoint differential. Establishes the minimum differential between cooling mode and
heating mode setpoints (by default 1 ºC / 2 ºF).
•
Mode switching protection (min). Allows you to define the minimum operating time
before allowing a change of mode, by default 30 min.
Limits. By default it is disabled. Once it is enabled, it allows you to set the maximum
temperature for heating mode and the minimum temperature for cooling mode.
IAQ Ranges. (AirQ Box only) Allows you to define the IAQ measurement ranges (upper and
lower).
* Not available in Bluetooth configuration.
EN
9