Every time a transmitter is programmed, the equipment will issue an acoustic signal for 0.5 sec.
After 10 seconds without programming or by pressing the programming button, the equipment will exit programming mode,
issuing two 1 sec. acoustic signals. If, on programming a transmitter, the equipment memory is full, it will issue seven 0.5
sec. acoustic signals and exit programming.
4. Set transmitters distance activation.
The unit is supplied with the activation distance set at the minimum.
Turn the potentiometer clockwise (to + position) to increase the activation distance
of the transmitters.
Turn the potentiometer to – position to decrease the activation distance of the transmitters.
It is the responsibility of the installer that the selected distance allows the user to have direct view of the door as it is in
motion.
It is recommended to mark this distance with the door closed, and then to verify that the door can be opened and closed
from both sides of it.
If the dead man transmitter is not situated in the activation zone, the LED blinks and three beeps will be heard. In this case
it is necessary to increase the activation distance.
1. « the person operating the door must have a direct view of the doorway, must be near the
door (5 meters maximum) during movement of the door and should not find itself in a
dangerous position »
Any adjustment of the radio range out of these recommendations, undertakes the installer in
terms of responsibility for injury or damage.
2. « Releasing of the pressure maintained control device should stop the door movement before
it scrolls 5cml » This implies a maximum speed of the door of 12.5 cm / s.
5. Verify the installation.
Perform a complete operation from both sides of the door ensuring that activation of the control panel is correct on
the desired coverage area, and ensuring that you can not activate the door without seeing it.
Check that the motor wiring is correct, and that the semi-automatic mode works in the open way (and not in the close way).
OPERATING
Upon receiving a code, the equipment checks whether it is in its memory, activating the opening or closing of the door.
-
In dead man operating, only it is activated inside the coverage area.
If the dead man transmitter is not inside the coverage area, the led will flash and the equipment will emit three acoustic
signals.
-
In semi-automatic operating, the open pushbutton opens in semi-automatic mode (2 minutes), without being inside the
coverage area. The close pushbutton will stop the motor at any distance, and then can close the door in dead man mode,
provided it is operated from inside the coverage area.
-
During the closing movement, if the dead man transmitter leaves the coverage zone, the door stops.
RESET TOTAL
In programming mode, the programming button is held down and a short-circuit on MR jumper is done for over 10 sec. The
equipment will issue 10 short acoustic warning signals followed by others at a faster pace to indicate that the operation has been
successful. The equipment is now in programming mode. The pilot programming light will also follow the acoustic indications by
flashing.
After 10 seconds without programming or quickly pressing the programming button, the equipment will exit programming mode,
issuing two 1 sec. acoustic signals.
ROLL868 DMR / ROLL868 DMR-P
WARNING: In accordance with the EN 13241-1 and EN 12453-1
standard concerning pressure maintained control devices:
-
+
8