PBS-10
Power supply for 12v SHERPA and ARAS centralized beacons.
The basic operation of the unit is as follow:
• WHEN MAINTAINED, charges the battery, controls the MAINS voltage and supplies -6V DC voltage to the beacons which are connected to the
unit. A LED pilot (inside) acts as a charging control. By connecting a DAISALUX remote-control (optional) to the unit and pressing ON,
it is possible to simulate a failure of the mains supply and so test its operation in emergency mode.
• DURING A MAINS FAILURE: the unit changes automatically to emergency operation mode, supplying 12V DC voltage to the beacons which are
connected to the unit for a period of time equal or superior to the rated duration of the unit. By connecting a DAISALUX remote-control
(optional) to the unit and pressing ON-OFF, emergency operation mode can change to stand-by mode and vice versa.
By connecting an extra push-button ("Stop push-button": see wiring diagram) and pressing it, emergency operation mode can change to stand-
by mode.
Assembly and installation instructions
REMOVE THE COVER OF THE UNIT. SCREW IT TO THE WALL, REMOVE
THE TAP FROM THE WIRING ENTRY HOLE. INTRODUCE THE WIRING INTO
THE UNIT AND COMPLETE THE ELECTRIC WIRING.
Specifications
Maintenance and caution
- All units are provided with a NiCd accumulators battery for the storage of energy. The manufacturers of these batteries assure a four
years operating life for the battery, or a minimum of 400 charge-discharge cycles. After this period, the batteries must be replaced to
keep unchanging the characteristics of the unit. The replacement of the batteries must be carried out by qualified personnel.
- Nominal voltage, duration and the characteristics of the battery are indelibly marked on the label of the unit.
- Any maintenance procedure must be carried out by qualified personnel.
- Before connection of the unit, always check that the voltage of the distributing mains supply corresponds with that specified on the
label of the unit.
- Be sure the unit is disconnected from the MAINS before performing any maintenance procedure.
- In order to prevent an excessive voltage drop in the electric wiring, the length of the cable connecting the PBS-10 with the beacons
should not exceed 75 metres, for 1.5 mm
sectional area or connect several cable lines to the beacons.
- It is not adviceable to disconnect the mains of the unit everyday, as the life of the batteries and the lamps will be reduced.
- Keep these instructions.
NOTE: PAY CAREFUL
ATTENTION TO THE POLAR-
ITY OF THE BEACONS.
diameter wires (15% total drop). If longer cables are desired, either use wires of bigger cross-
2
www.daisalux.com
- THE UNIT MUST BE FED BY THE MAINS SUPPLY.
- CHECK THAT THE INSIDE LED IS ON.
- CHECK THAT ALL LED PILOT LIGHTS OF THE BEACONS ARE ON.
- PLACE THE COVER AND SCREW IT IN WITH THE SAME SCREWS
LOOSENED BEFORE.
Power supply ................................ See label.
Output power (emergency mode) ........<15W
Batteries ....................................... Sealed NiCd.
Remote-control voltage ...............
Fuses:
F1 (Mains)............
F2 (Beacons)..........
F3 (Battery)............
Class ............................................ II
IP
.............................................. 20
Maximum beacon number .......... 10 items.
24h
± 12 V DC.
0,125 Amp.
0,5 Amp.
4 Amp.