INSTRUCTION SHEET
ESE MANUAL TESTER SIXXI, (SI-TESTER)
Description and purpose
Easily test on-site the state of an nVent ERICO System 1000 Early Streamer Emission Terminal, SIXXi models.
The test result is displayed in summary with display of the <OK> (green led) or <Default> (red led).
The tester is self-contained and operates on a standard 9 V battery, type PP3, which is placed on the back of the case. In
case of battery failure, <Bat> lights up intermittently (yellow led) then the battery needs to be changed.
Function of buttons and indicators
1
3
2
4
5
5
Electrical Specifications
•
Test of the lightning conductor circuit with impulses
•
Max voltage: 1.2 kV
•
Max current: 100 A
Mechanical characteristics
•
Waterproof plastic case: IP56
•
Dimension: L 149 mm, D 89 mm, H 26 mm
•
Weight: 280 g
•
Supplied with two test leads fitted with crocodile clips.
•
The SI-TESTER-POLE is a deployed telescopic pole of 9m long (folded length: 2.55m) in order to reach ESE
terminals at 10m height.
Instructions
The use on site is limited to the connection of the red terminal of the tester to the tip of the Terminal (directly by alligator clip
or via the white cable of the SI-TESTER-POLE and the second in black, by alligator clip, to the body of the ESE, or to its
mast, or to the nearest down conductor to which it is connected.
The test is carried out by pressing the 2 buttons with the nVent logo present on the housing (with both hands so as not to
touch the lightning terminal during the test) for a period of approximately 6 seconds, until the result appears of the test
resulting in the green flashing led <OK> or red <Default>.
WARNING:
1. nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at www.nVent.com and from your nVent
customer service representative.
2. nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and/or death,
and void your warranty.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and
gloves as appropriate to the application.
nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the
property of their respective owners. nVent reserves the right to change specifications without prior notice.
TECHNICAL SUPPORT:
www.nVent.com
1.
Connection terminals for cables connecting to the Early Streamer Emission Terminal
2.
Flashing red light indicates at the end of the test that the ESE terminal is in poor condition.
3.
Flashing green light indicates at the end of the test that the ESE terminal is in good condition
4.
Yellow light indicating the state of the battery. LED on for "battery OK" and flashing for
"battery to be replaced"»
5.
Test launch buttons