5.
Refrigerant pipes' exhaust
5.1 Connection diagram
Vapour valve
Vapor valve
CLOSE
Liquid valve
CLOSE
Refrigerant equipment
5.2 Ready for operation
Connect the pipes correctly and firmly. (Please refer to the connection diagram)
1. Open the vapour and liquid valves of manifold gauge.
2. Close the vapour and liquid valves of tank.
3. Loosen the connecting pipes of refrigerant tank.
4. 0pen the valve of pipes.
5.3 Start operation
5. Turn the switch to position "START".
6. Press
button.
7. Turn the switch to position "2" and start exhausting the air of inside pipes.
8. While the input gauge getting to -1bar ,turn the switch to position "3" to start self-purge.
9. While the input gauge getting to -1bar again, turn the switch to position "0" OFF to finish self -purge.
10. Connect the pipes to refrigerant tank.
5.4 Finish operation
11. Press "O" button.
Recover slow
Liquid valve
OPEN
OPEN
Dry filter
Manifold gauge
ENGLISH
Recover fast
START
Purga
OFF
Button
CLOSE
Unit
LOOSEN
START
CONNECT
CLOSE
Vapor valve
80% O.F.P.
connecting line
Refrigerant tank
OPEN
CLOSE
Liquid
valve
17