Descargar Imprimir esta página

Minebea Intec YDO02C-232 Instrucciones De Instalación página 14

Ocultar thumbs Ver también para YDO02C-232:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Terminating resistors
for Profibus
GND
390 O
A
220 O
B
390 O
VP
4
1
2
3
4
1
3
2
4
1
2
3
YDO02C
14
4
1
YDO0...-DP (Option B1)
Equipment Supplied
– Interface module
– Installation instructions (this manual)
– "Field bus" software interface description
– GSD file: see Minebea Intec website "Minebea Intec Mechatronics Software download:
Select product: Fieldbus files"
Assembly
Connect interface module YDO0...-DP (Profibus interface) directly to the digital board
of the scale, without configuration. For more information, please refer to the section
entitled "Installing in the Indicator". Any terminating resistors that may be necessary for
the bus system must be installed outside the indicator. The voltage required for this is
supplied internally by the indicator. A bus connection is required at both ends of the bus
system. This is achieved either by
– Termination within the connecting plugs (at baud rates > 1.5 Mbit/s with additional
inductances)
or by
– Internal bus terminations.
Use switches 1 through 4 to set the particular resistor:
Operating status
390 ohms bias resistor against GND
220 ohms terminating resistor
220 ohms terminating resistor
390 ohms bias resistor against 5 V
Note: SW 1–2 and SW 1–3 – or all switches – must be activated simultaneously.
0.2A
OUTx_high
Use the 5V supply voltage only for activating external bias resistors in accordance with
LV1
the Profibus-DP specification.
30V
Notes:
!
Only use cables and plugs that conform to the Profibus specification.
!
Connect the shielding of the connecting cable to the housing.
OUTx_low
LV1
Example: Basic wiring diagram
Inputx_high
LV2
Inputx_low
LV2
0.2A
OUTx_high
LV1
30V
OUTx_low
LV1
Inputx_high
LV2
Switch
SW 1–1: ON
SW 1-2: ON
SW 1-3: ON
SW 1-4: ON
YDO0...-DIO, Option A5: Specifications
Digital inputs
– Quantity:
5
– Low level:
-3 V to +5 V
– High level:
+11 V to +30 V
– Maximum current
consumption:
2.6 mA at 15 V
– Switching of inputs by applying the correct voltage.
Digital outputs
– Quantity:
5
– Maximum current conduction per channel: 100 mA
– Voltage range:
0-30 V DC
– Each output is created by an optoelectronic coupler.