Technical features
Description and functions
Oil level (Float)
The device indicates any gas evolvement or oil level variation.
- Slight oil level variation or any insignificant gas evolvement is denoted by the
float position between "MIN" & "MAX" on the display.
- At major oil variation level or gas evolvement the float stops at "MIN" and
opens/closes the alarm circuit.
- Any accumulated gas can be drawn off by the valve provided.
Pressure (Pressure switch)
This feature measures the internal pressure of transformer. The normal level is
to be set by the user according to the transformer manufacturer's instructions.
When pressure exceeds a pre set level the alarm circuit is triggered by a change
over contact.
Temperature
"T2" Thermostat switch (Alarm)
The feature measures the internal oil temperature of the transformer.
The normal operating value is to be set by the user according to the transformer
manufacturers instructions. At a pre set temperature the alarm circuit is triggered
by a change over contact (T2).
"T1" Thermostat switch (Stop)
The feature measures the internal oil temperature of the transformer.
The normal operating value is to be set by the user according to the transformer
manufacturers instructions. At a pre set temperature the stop circuit is triggered
by a change over contact (T1).
Thermometer
The device measures the internal temperature of the transformer, which shall
be visualized outside the device through the protection window.
The thermometer is equipped with a drag pointer.
Table 2
General feature
Degree of protection (EN 60529)
Suitable for Offshore application
UV-Ray resistance (UNI-ISO 4892 / UNI-ISO 4582)
Measuring range
Environment temperature
Cable connection
Cable box (EN 50005 / EN 60947-7-1 / IEC 947-7-1)
Wire section to be used on clamp box
Max. rated pressure
Electrical characteristics
Table 3
Current
Circuit type
Voltage
Electric rating
Oil level
Pressure switch
Thermostat
Table 4
Analogue Output
Temperature
Pressure
Max distance for analougue output
* -1000/+1000 mbar - 4/20 mA is available on demand
Table 5
8
IP66
1000 h
500 h
40°C to +120°C
-40°C to 55°C
M 25 x 1.5
According to standard
Up to 2.5 mm
500 mbar, different pressure are available on demand. Contact us for other options
(comemservice@it.comem.com)
Double insulation
ac
Ohmic
Ohmic inductive
(cosφ > 0,5)
220
127
24
220
2A
2A
2A
2A
6A
6A
6A
2A
16A
16A
16A
4A
4-20 mA proportional to the measuring temperature range (0°C-4 mA.... 160°C-20 mA)
4-20 mA proportional to the pressure range (0 mbar - 4 mA ... 500 mbar - 20mA)*
Max 30 m / 98 ft. Contact us for other options (customerservice@it.comem.com)
Measure
Max 150 cm
100 mbar to
500 mbar
30°C to 120°C
30°C to 120°C
30°C to 160°C
2
dc
Ohmic
127
24
220
2A
2A
2A
2A
2A
0,6A
4A
4A
0,6A
INTEGRATED SAFETY DEVICES eRIS2
Checking test value
Locate the magnet close to the float
3
(between MAX and MIN). Drawn it
downwards until it reaches "MIN".
To reset the float to its correct
position draw the magnet upwards
and detach.
With the internal pressure at least
100mbar set the adjusting knob of the
pressure switch to minimum.
Open the rear cover using both hands,
do not lever at one side only.
The adjustment knob of the alarm
switch "T2" should be set to the
minimum value.
The adjustment knob of the stop
switch "T1" should be set to zero.
The adjustment knob of the stop
switch "T1" should be set to the
minimum value.
The protection window is to be
unscrewed so that the pointer shall
be set to the minimum values.
Ohmic inductive
(L/R < 40ms)
127
24
220
2A
2A
2A
0,6A
0,6A
0,6A
0,6A
0,6A
0,2A
127
24
2A
2A
0,6A
0,6A
0,3A
1,8A