Secure the electrical wiring with cable ties as shown
in the figure in 10.2 .
Make sure no external pressure is applied to the
terminal connectors.
When installing the earth leakage circuit breaker make
sure that it is compatible with the inverter (resistant to
high frequency electrical noise ) to avoid unnecessary
opening ofthe earth leakage circuit breaker.
As this unit is equipped with an inverter, installing a
phase advancing capacitor not only will deteriorate
power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-
frequency waves. Therefore, never install a phase
advancing capacitor.
CAUTION
Be sure to install the required fuses or circuit
breakers.
10.2. Connecting power supply and inter-
unit wiring
Connect and fix the power supply cable, indoor-
outdoor connection cable as following:
Power supply:
380-415V,3N~,
50/60Hz
For three phase power supply models:
1U105S2SS1FB 1U125S2SN1/2FB 1U140S2SN1FB
1U140S2SP1/2FB 1U160S2SP1FB
Power supply cable:
2
H05RN-F 5G 4mm
,
Indoor and outdoor connection cable:
2
H05RN-F 4G 2.5mm
£n-
outdoor unit connection cable length L satisfied
condition 40m< L<55m, please change the connection
cables specification to H07RN-F 4G 4.0mm
indoor and outdoor unit connection cable length L
satisfied condition 55m< L1<75m, please change the
connection cables specification to H07RN-F 4G 6.0mm
£'
Outdoor unit
terminal blocks
1U105S2SS1FB
1U125S2SN1/2FB
1U140S2SN1FB
1U140S2SP1/2FB
1U160S2SP1FB
Indoor unit
terminal blocks
1
Note
Ifthe indoor and
£"
2
. If the
Power supply:
1PH,220-240V~,
50/60Hz
For single phase power supply models:
1U105S2SS1FA,1U105S2SS2FA,
Power supply cable: H05RN-F 3G 4.0mm
1U125S2SN1FA,1U125S2SN2FA,1U140S2SP2FA,
1U140S2SN1FA,1U140S2SP1FA
Power supply cable: H05RN-F 3G 6.0mm
Indoor and outdoor connection cable: H05RN-F 4G 2.5mm
1
£n-
Note£" If the indoor and outdoor unit connection
cable length L satisfied condition 40m< L<55m, please
change the connection cables specification to H07RN-F
2
4G 4.0mm
. If the indoor and outdoor unit connection
cable length L satisfied condition 55m<L<75m, please
change the connection cables specification to H07RN-F
2
4G 6.0mm
£'
Fix the cable with the clip to prevent slide.
Clip
Outdoor-indoor unit
connection cable
Secure the cable to the stop valve attachment plate
so that it does not slide.
When cables are routed from the unit, a protection
sleeve for the conduits (PG-insertions) can be
inserted at the knock-out hole.
When you do not use a wire conduit, be sure to
protect the wires with vinyl tubes to revent the edge of
the knock-out hole from cutting the wires.
Follow the electric wiring diagram for electrical wiring
2
works.
20
Outdoor unit
terminal blocks
1U105S2SS1/2FA
1U125S2SN1/2FA
1U140S2SN1FA
1U140S2SP1/2FA
Indoor unit
terminal blocks
2
2
Clip
Power supply cable
2