ENGLISH
VARIABLES
r0
Temperature difference compared to main SETPOINT
d0
Defrost interval (hours)
End-of-defrost setpoint. Defrost is not executed if the temperature
d2
read by the defrost sensor is greater than d2 (If the sensor is faulty
defrosting is timed)
d3
Max defrost duration (minutes)
Drip duration (minutes) At the end of defrost the compressor and
fans remain at standstill for time d7, the defrost LED on the front
d7
panel flashes.
Fan pause after defrosting (minutes). It allows fans to be kept at
standstill for a time F5 after dripping. This time begins at the end of
F5
dripping. If no dripping has been set the fan pause starts directly at
the end of defrost.
Minimum temperature alarm. It allows user to define a minimum
temperature for the room being refrigerated. Below value A1 an
A1
alarm trips: the alarm LED flashes, displayed temperature flashes
and the buzzer sounds to indicate the problem.
Maximum temperature alarm. It allows user to define a maximum
temperature for the room being refrigerated. Above value A2 an
A2
alarm trips: the alarm LED flashes, displayed temperature flashes
and the buzzer sounds to indicate the problem.
tEu
Evaporator sensor temperature display (displays nothing if dE=1)
VARIABLES
F3
Fan status with compressor off
F4
Fan pause during defrost
Evaporator fans activation for air recirculation.
The fans activate for a time defined by F7 if they
F6
have not started working for the F6 time. If
activation time coincides with the defrosting
time, end of defrosting is awaited.
Evaporator fans duration for air recirculation.
F7
Fans working time for F6
Sensor presence. If the evaporator sensor
is disabled defrosts are carried out cyclically
dE
with period d0: defrosting ends when an
external device trips and closes the remote
defrost contact or when time d3 expires.
FUNCTION
View set point
Change set point
Change menu "User level"
Return
Change menu "Installer level"
Return
LIST OF LEVEL 1 VARIABLES (User level)
MEANING
LIST OF LEVEL 2 VARIABLES (Installer level)
MEANING
ECP202 BASE – Parameters Abstract
Rev. 01-21
PRESS
+
/
+
(3 seconds)
+
(3 seconds)
+
+
(3 seconds)
+
(3 seconds)
VALUES
0 = Fans run continuously
1 = Fans only run when compressor is working
2 = Fans disabled
0 = Fans run during defrost
1 = Fans do not run during defrost
0 ÷ 240 min
0 = (function not activated)
0 ÷ 240 sec.
0 = evaporator sensor present
1 = no evaporator sensor
VALUE
DEFAULT
0.2 ÷ 10 °C
2°C
0 ÷ 24 hours
4 hours
-35 ÷ 45 °C
15°C
1 ÷ 240 min
25 min
0 - 10 min
0 min
0 - 10 min
0 min
-45 ÷ (A2-1) °C
-45°C
(A1+1) ÷ 99 °C
+99°C
temperature
read only
DEFAULT
0 min
10 sec
Pag. 3
1
1
0