LEGRAND LEXIC 0046 83 Manual De Instrucciones página 10

Publicidad

(1) ---------------------------------------------------------------------------------
0 : PF = 0 or 1
1 : ind
2 : cap
(2) ---------------------------------------------------------------------------------
0 : positive
1 : negative
(3) ---------------------------------------------------------------------------------
WRITABLE ONLY
0x01 : reset partial active energy
0x02 : reset partial reactive energy
0x08 : reset operating timer
0x10 : reset peak maximum demand
Example
Address
Description
Byte n.
0x1000
Long
Phase 1 : phase voltage
Address 1000: 3
Address 1001: 33492
Phase1, Phase voltage: 3 x 2
COMMUNICATION PROTOCOL
16
+ 33492 = 230100mV
Unit
mV
pag. 2/2