STORAGE
For storing the air compressor, be sure to do the following:
1. Turn the unit off and unplug the power cord from the receptacle.
2. Remove all air hoses, accessories, and air tools from the air compressor.
3. Perform the daily maintenance schedule.
4. Open the drain valve to bleed all air from the tank.
5. Close the drain valve.
6. Protect the electrical cord and air hose from damage (such as being stepped
on or run over). Wind them loosely around the compressor handle.
7. Store the air compressor in a clean and dry location.
Risk of Unsafe Operation. Unit cycles automatically
when power is on. When servicing, you may be exposed to voltage sources,
compressed air, or moving parts. Before servicing unit unplug or disconnect
electrical supply to the air compressor, bleed tank of pressure, and allow
the air compressor to cool.
PROBLEM
Low pressure or
not enough air
or Compressor
does not stop.
Air leaks from
regulator, or
regulator does
not regulate
pressure.
TROUBLESHOOTING
CAUSE
Tank drain valve is open. Close drain valve.
Fittings leak.
Restricted air intake.
Prolonged excessive
use of air.
Compressor not
large enough.
Hole in air hose.
Tank leaks.
Blown seals.
Valve leaks.
Leaking or worn piston.
Dirty or damaged
regulator internal parts.
Check fittings with soapy water.
Tighten or reseal leaking fittings.
DO NOT OVERTIGHTEN.
Clean or replace intake filter element.
Decrease amount of air used.
Check air requirement of accessory.
If it is higher than CFM and
pressure supplied by compressor,
you need a larger compressor.
Most accessories are rated at 25% of
actual CFM while running continuously.
Check and replace if necessary.
tank. DO NOT attempt to repair.
Replace seals.
Replace seals.
Replace piston.
Replace regulator or internal parts.
17 - ENG
CORRECTION
Immediately replace