Network parameters setting
Setting network parameters via DHCP
Step
Action
1
Install EM24
2
Enable DHCP and exit with End
3
Connect the EM24 to the LAN network to which the PC is connected
Access the Info pages to view the assigned network parameters
4
5
Start UCS software and connect to EM24 via Manual connection> Modbus TCP
6
Enter the IP address displayed on the Info page (see point 4)
7
Access the settings, disable DHCP and assign the required network parameters (assigned by network administrator)
Setting network parameters without DHCP
Step
Action
1
Install EM24
2
Disable DHCP (default setting)
3
Connect the PC to the EM24 via Ethernet cable (point to point connection)
Set the PC network properties as follows:
•
static IP address
•
IP address of the same class as the EM24, e.g. if the IP of EM24 is 192.168.1.10 (default), you can set the PC address to
4
192.168.1.20
•
Subnet mask: 255.255.255.0
•
Gateway: not necessary
Start UCS software and connect to EM24 via Manual connection> Modbus TCP, enter the EM24 IP address
5
(192.168.1.10 by default)
6
Access the settings and enter the required network parameters
7
Disconnect the Ethernet cable and connect the EM24 to the network to which the Modbus master is connected
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA